14 freeze protection (default: enabled) – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 128

Advertising
background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.3.14 Freeze Protection (Default: Enabled)

Figure 18-18: FREEZE PROTECTION Menu

Freeze Protection allows the freeze protection feature to be enabled and disabled. Press the UP

or DOWN buttons to select Enabled or Disabled then press the OK button to store the setting.

Enabled:

The Freeze Protection feature is enabled to protect the boiler from freezing. This

feature monitors the boiler water temperature and responds as follows when no call is present:

46°F [8°C]: Auxiliary Boiler Pump ON

42°F [6°C]: CH(1), Auxiliary Boiler & System Pumps ON. Burner operates at low fire.

60°F [15°C]: Freeze protection ends. Burner & all pumps OFF after completing CH Post

Pump Time.

Disabled:

The Freeze Protection feature is disabled.

WARNING!

Freeze Protection should only be disabled when the system

contains antifreeze to prevent the system from freezing. Serious

damage could occur to the boiler as well as the entire heating

system if freeze Protection is disabled without antifreeze in the

system.

The boiler should NEVER be installed in a location where

freezing could occur. Subjecting the boiler to freezing conditions

could lead to freezing of the condensate, and the possibility of

causing serious injury or death.







Page 128 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14