GF-135 Esteem 399 Low NOx Boiler

Chapter 10

OMM-0089_0A

Installation, Operation & Maintenance Manual EZ-SET Controller

10.6 EZ SETUP

Navigation: Home Screen > Main Menu > EZ Setup

The EZ Setup menus provide a simple way to quickly customize the controller for each

installation. EZ Setup prompts the user to make selections which allows the Esteem 399 boiler

to be setup very quickly without searching through long lists of settings and manually making

adjustments.

10.7 HEATING EZ SETUP

Navigation: Home Screen > Main Menu > EZ Setup > Heating EZ Setup

Heating EZ Setup allows the installer to quickly customize the central heating settings for the

application.

10.7.1 Select CH Demand (Default: Switch & Outdoor Reset)

Select CH Demand prompts the installer to select how a CH Demand is generated. Press the

UP or DOWN buttons to select the CH Demand type then press the OK button to store the

setting. The Select CH Demand options are:

Switch & Outdoor Reset: This option is only displayed when the outdoor temperature

sensor is connected. A central heating call from a thermostat or zone panel will enable

the Esteem and the setpoint will vary with the outdoor temperature for central heating

calls.

Switch & Setpoint: This option is only displayed when the outdoor temperature sensor is

not connected. A central heating call from a thermostat or zone panel will enable the

Esteem and the setpoint will be fixed for central heating calls

Constant & Outdoor Reset: This option is only displayed when the outdoor temperature

sensor is connected. The Esteem will maintain set-point without an external call from a

thermostat or zone panel. The set-point will vary with the outdoor temperature for central

heating calls.

Constant & Setpoint: The Esteem will maintain setpoint without an external call from a

thermostat or zone panel. The setpoint will be fixed for central heating calls.

0-10V Modulation Signal: This option allows the Esteem firing rate to be controlled by

an external control system.

Figure 10-6: Select CH Demand Menu (with Outdoor Sensor & Without)