GF-135 Esteem 399 Low NOx Boiler

Chapter 10

OMM-0089_0A

Installation, Operation & Maintenance Manual EZ-SET Controller

10.8.3 DHW Storage Setpoint (Default: 140°F [60°C])

DHW Storage Setpoint prompts the installer to enter the domestic hot water storage setpoint

temperature when the Sensor option is chosen in Select DHW Demand. Press the LEFT or

RIGHT buttons to adjust the DHW Storage Setpoint then press the OK button to store the

setting.

Figure 10-12: DHW Storage Setpoint Menu

NOTE

The Boiler DHW Setpoint will automatically be set 46°F [25°C]

higher than the DHW Storage Setpoint setting.

10.8.4 DHW Priority Timeout (Default: Off)

DHW Priority Timeout prompts the installer to enter an optional time limit that a domestic hot

water call has priority over a central heating call. Press the LEFT or RIGHT buttons to adjust the

DHW Priority Timeout then press the OK button to store the setting.

Figure 10-13: DHW Priority Timeout Menu