Combustion Air/Venting

3.5.2 OUTDOOR COMBUSTION AIR

The minimum dimension of air openings for outdoor combustion air venting shall be not

less than 3 inches.

3.5.2.1 Option 1: One Permanent Opening to Outside
Openings used to supply combustion and ventilation air shall be sized and located in

accordance with the following:

•

One Permanent Opening Method. See Figure 3-2.

•

One permanent opening, commencing within 12 inches of the top of the enclosure,

shall be provided. The equipment shall have clearances of at least 1 inch from the

sides and 6 inches from the front of the appliance. The opening shall directly

communicate with the outdoors or shall communicate through a vertical or horizontal

duct to the outdoors or spaces that freely communicate with the outdoors and shall

have a minimum free area of the following:

Figure 3-2:

All Combustion Air from Outdoors Through One Permanent Air Opening

•

1 sq. in./3000 Btu/hr. of the total input rating of all equipment located in the enclosures,

and

•

Not less than the sum of the areas of all vent connectors in the space.