Chapter 10: basic ez-set controller operation, 1 ez-set controller introduction, 2 ez-set controller features and functions – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 65: Chapter 10, Basic ez-set controller operation

Advertising
background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 10

OMM-0089_0A

Installation, Operation & Maintenance Manual EZ-SET Controller

CHAPTER 10: BASIC EZ-SET CONTROLLER OPERATION

NOTE

This chapter describes the general operation of the EZ-SET

controller. See Chapter 18 for in-depth information concerning

controller installer setup, operation, and menus.

10.1 EZ-SET CONTROLLER INTRODUCTION

The Esteem Boiler Management System is designed to be flexible yet easy to use. The

controller monitors and controls the Esteem boiler to operate as efficiently as possible. The

controller monitors the boiler supply, return and flue gas temperatures and operates the igniter,

gas valve and blower and uses this information to modulate the boiler’s firing rate to maintain the

required setpoint. All controller features are easy to use through a graphical display where

information is presented either graphically or in plain English, so code charts are not required.

Figure 10-1 shows an image of the EZ-SET controller front panel, including menu display,

navigation buttons, ON/OFF switch, Installer button, and temperature gauge.

10.2 EZ-SET CONTROLLER FEATURES AND FUNCTIONS

The EZ-SET controller offers many advanced control options, which may be adjusted for various

applications to achieve optimum boiler efficiency and operation, and includes:

Two central / space heating (CH) call inputs with separate outdoor reset curves.

Domestic Hot Water (DHW) call input with optional priority.

EZ Setup feature allows the installer to quickly customize the EZ-SET controller for each

installation.

Cascade function allows up to six boilers to operate together in a single heating system.

Modbus interface for integrating with building management systems.

These advanced features are adjustable in the Installer Menu after entering an access

code.



















Figure 10-1: EZ-SET Controller Front Panel Features

Installer Button

Navigation Buttons

ON/OFF Switch

Menu Display

Pressure Gauge

Page 65 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288

Advertising