18.9.10 CH Proportional Gain (Default: 7)

CH Proportional Gain allows the cascade response to be adjusted for a central heating call. CH

Proportional Gain has the greatest influence when the system temperature is far away from the

setpoint. Press the LEFT or RIGHT buttons to adjust the CH Proportional Gain then press the

OK button to store the setting.

Figure 18-61: CH Proportional Gain Menu

Increase CH Proportional Gain:

The Cascade System will reach setpoint faster, but overshooting the setpoint may occur.

To reach the setpoint faster, increase the CH Proportional Gain value by 2. Perform

Cascade Auto-detection and initiate a central heating call. Observe the cascade response

and make further adjustments if necessary.

Decrease CH Proportional Gain:

The Cascade System will take longer to reach the setpoint, but setpoint overshooting is

minimized.

If the setpoint is reached too quickly, decrease the CH Proportional Gain value by 2.

Perform Cascade Auto-detection and initiate a central heating call. Observe the cascade

response and make further adjustments if necessary.

NOTE

Only make adjustments to this setting after consulting AERCO

Technical Support. Improper adjustment of CH Proportional Gain

could lead to temperature fluctuations and erratic cascade

operation.