GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.3.3 Absolute Max CH Setpoint (Default: 188°F [87°C])

Figure 18-9: ABSOLUTE MAX CH SETPOINT Menu

Absolute Max CH Setpoint limits the setpoint during a central heating call. This setting can be

used to prevent a user from adjusting the central heating setpoint or outdoor reset curve above

a safe operating temperature in the EZ Setup Menu. A warning screen will be displayed in EZ

Setup if the user attempts to raise the setpoint above the Absolute Max CH Setpoint. The

Absolute Max CH Setpoint will be displayed on the outdoor reset curve in EZ Setup if the user

selects an outdoor reset curve which goes above the Absolute Max CH Setpoint. Press the

LEFT or RIGHT buttons to adjust the Absolute Max CH Setpoint then press the OK button to

store the setting.
=======================================================================

18.3.4 CH1 Maximum Setpoint (Default: 180°F [82°C])

Figure 18-10: CH1 MAXIMUM SETPOINT Menu

CH1 Maximum Setpoint is the maximum setpoint for a CH1 heating call when an Outdoor

Reset option is chosen in CH Demand. CH1 Maximum Setpoint is the fixed setpoint for a CH1

heating call when a Setpoint option is chosen in CH Demand. Press the LEFT or RIGHT

buttons to adjust the CH1 Maximum Setpoint then press the OK button to store the setting.




Page 123 of 188