Installation, Operation & Maintenance Manual

Start-Up Procedures

12.3.1 Troubleshooting Start-Up Problems

If the Esteem boiler does not start correctly, follow the procedures below to troubleshoot the

problem.

Troubleshooting Start-Up Problems

1. Check for loose electrical connections, blown fuses, (on control module and in terminals) or

an open service switch.

2. Verify CH and DHW operation is enabled. A radiator or faucet icon with an X through it

indicates that function is disabled.

3. Check continuity across the LWCO device for a closed circuit. See item 6 in Figure A-2 in

Appendix A.

4. Is an external limit control (if applicable) open? Ensure the external limit is reset to the

closed position.

5. Are the gas supply valves open at the unit and meter?

6. Is incoming gas supply pressure at the unit more than 5”W.C. and less than 13” W.C. for

natural or propane with all gas appliances ON or OFF.

7. Are the heating thermostats set above room temperature?

If none of these conditions correct the problem, refer to the Esteem boiler Trouble-Shooting

Guide or contact AERCO Technical Services.

12.4 INSPECTION OF THE ESTEEM BOILER AND SYSTEM

12.4.1 Boiler Piping inspection

Inspect the Boiler system piping and components for leaks. If found, shut down the unit and

repair immediately.
Purge any remaining air from the system piping. Air in the system piping will interfere with

circulation creating heat distribution problems and system noise.

12.4.2 Vent Piping and Combustion Air Piping inspection

Inspect for gas-tight seals at every connection and seam of the venting and combustion air

piping.

WARNING!

Venting system must be sealed gas-tight to prevent flue gas

spillage and potential carbon monoxide emissions, which will result

in severe personal injury or death.