GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

Table 18-10: Holding Registers (Read/Write) - Continued

Address

DEC (HEX)

Supported

Commands

Description

Byte:

Format

Notes

514 (0x202)

0x03

0x06

0x10

CH Setpoint

LB:U8

Value = CH Setpoint °C.

This register becomes active when 255

is written to register 512 (0x0200).

1280 (0x0500)

0x03

CH1 Maximum

Setpoint

LB:U8

Value = °C

1281 (0x0501)

0x03

DHW Storage

Setpoint

LB:U8

Value = °C

0 (0x0000)

0x04

Boiler Status

LB: Flag8

Bit: Description

0: PC Manual Mode

1: DHW Mode

2: CH Mode

3: Freeze Protection Mode

4: Flame Present

5: CH(1) Pump

6: DHW Pump

7: System / CH2 Pump

0 = Off, 1 = On

1 (0x0001)

0x04

Lockout Status

MB:

Flag8

LB:U8

Bit: Description

1: Lockout Code Type

0 = Automatic Reset Lockout

1 = Manual Reset Lockout

Value = Lockout Code

2 (0x0002)

0x04

Lockout Status

LB:U8

0 = Single / Master Boiler

1 = Slave 1

2 = Slave 2

3 = Slave 3

4 = Slave 4

5 = Slave 5

F = Single / Master Display

768 (0x0300)

0x04

Boiler Supply

Temperature

/System

Temperature

S16

Value = 0.1°C

Invalid Value = 32768 (0x8000).

Value is the Boiler Supply Temperature

unless the System Temperature

Sensor is installed.

769 (0x0301)

0x04

Boiler Return

Temperature

LB:S8

Value = °C.

Invalid Value = 65472 (0xFFC0).

770 (0x0302)

0x04

DHW Storage

Temperature

LB:S8

Value = °C.

Invalid Value = 32768 (0x8000).

771 (0x0303)

0x04

Boiler Flue

Temperature

LB:S8

Value = °C.

Invalid Value = 65472 (0xFFC0).

772 (0x0304)

0x04

Outdoor

Temperature

LB:S8

Value = °C.

Invalid Value = 32768 (0x8000).

773 (0x0305)

0x04

Future Use

LB:U8

774 (0x0306)

0x04

Flame Ionization

Current

LB:U8

Value = Flame Current µA.

775 (0x0307)

0x04

Boiler / Cascade

Firing Rate

LB:U8

Value = Firing Rate %.

776 (0x0308)

0x04

Boiler Setpoint

LB:U8

Value = °C.

Invalid Value = 32768 (0x8000).