18.9.13 DHW Integral Gain (Default: 245)

DHW Integral Gain allows the cascade response to be adjusted for a domestic hot water call.

DHW Integral Gain has the greatest influence when the system temperature is close to the

setpoint. Press the LEFT or RIGHT buttons to adjust the DHW Integral Gain then press the OK

button to store the setting.

Figure 18-64: DHW Integral Gain Menu

Increase DHW Integral Gain:

The Cascade System will take longer to reach the setpoint, but setpoint overshooting is

minimized.

If the setpoint is reached too quickly, increase the DHW Integral Gain value by 2. Perform

Cascade Auto-detection and initiate a domestic hot water call. Observe the cascade

response and make further adjustments if necessary.

Decrease DHW Integral Gain:

The Cascade System will reach setpoint faster, but overshooting the setpoint may occur.

To reach the setpoint faster, decrease the DHW Integral Gain value by 2. Perform Cascade

Auto-detection and initiate a domestic hot water call. Observe the cascade response and

make further adjustments if necessary.

NOTE

Only make adjustments to this setting after consulting AERCO

Technical Support. Improper adjustment of DHW Integral Gain

could lead to temperature fluctuations and erratic cascade

operation.