For installations using two sensors, the duct smoke

detector does not differentiate which sensor signals an

alarm or trouble condition.

Smoke Detector Locations

Supply Air — The Supply Air smoke detector sensor is

located to the left of the unit’s indoor (supply) fan. See

Fig. 18. Access is through the fan access panel. There is

no sampling tube used at this location. The sampling tube

inlet extends through the side plate of the fan housing

(into a high pressure area). The controller is located on a

bracket to the right of the return filter, accessed through

the lift--off filter panel.

Smoke Detector Sensor

C08245

Fig. 18 -- Typical Supply Air Smoke Detector Sensor

Location

Return Air without Economizer — The sampling tube is

located across the return air opening on the unit basepan.

See Fig. 19. The holes in the sampling tube face

downward, into the return air stream. The sampling tube is

connected via tubing to the return air sensor that is

mounted on a bracket high on the partition between return

filter and controller location. (This sensor is shipped in a

flat--mounting location. Installation requires that this

sensor be relocated to its operating location and the tubing

to the sampling tube be connected. See installation steps

below.)

Return Air Detector Sampling Tube

Controller module

Return Air Detector module
(shipping position shown)*

*RA detector must be moved from shipping position to operating position by installer

C07307

Fig. 19 -- Typical Return Air Detector Location

Return Air with Economizer — The sampling tube is

inserted through the side plates of the economizer

housing, placing it across the return air opening on the

unit basepan. See Fig. 20. The holes in the sampling tube

face downward, into the return air stream. The sampling

tube is connected via tubing to the return air sensor that is

mounted on a bracket high on the partition between return

filter and controller location. (This sensor is shipped in a

flat--mounting location. Installation requires that this

sensor be relocated to its operating location and the tubing

to the sampling tube be connected. See installation steps

below.)

Return Air
Sampling Tube

C08129

Fig. 20 -- Return Air Sampling Tube Location

Completing Installation of Return Air Smoke

Sensor:

Flexible
Exhaust Tubes

Screws

Sample Tube

C08126

Fig. 21 -- Return Air Detector Shipping Position

1. Unscrew the two screws holding the Return Air

Sensor detector plate. See Fig 21. Save the screws.

2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out-

wards and the sampling tube connection is on the bot-

tom. See Fig 22.

4. Screw the sensor and detector plate into its operating

position using screws from Step 1. Make sure the

sampling tube connection is on the bottom and the ex-

haust tube is on the top. See Fig 22.

5. Connect the flexible tube on the sampling inlet to the

sampling tube on the basepan.