Caution – Carrier 50TCA04-A07 User Manual

Page 17

Advertising
background image

17

Sensor and Controller Tests
Sensor Alarm Test

The sensor alarm test checks a sensor’s ability to signal an

alarm state. This test requires that you use a field provided

SD--MAG test magnet.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
This test places the duct detector into the alarm state.

Unless part of the test, disconnect all auxiliary

equipment from the controller before performing the

test. If the duct detector is connected to a fire alarm

system,

notify

the

proper

authorities

before

performing the test.

CAUTION

!

Sensor Alarm Test Procedure

1. Hold the test magnet where indicated on the side of

the sensor housing for seven seconds.

2. Verify that the sensor’s Alarm LED turns on.
3. Reset the sensor by holding the test magnet against

the sensor housing for two seconds.

4. Verify that the sensor’s Alarm LED turns off.

Controller Alarm Test

The controller alarm test checks the controller’s ability to

initiate and indicate an alarm state.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
This test places the duct detector into the alarm state.

Disconnect all auxiliary equipment from the controller

before performing the test. If the duct detector is

connected to a fire alarm system, notify the proper

authorities before performing the test.

CAUTION

!

Controller Alarm Test Procedure

1. Press the controller’s test/reset switch for seven

seconds.

2. Verify that the controller’s Alarm LED turns on.
3. Reset the sensor by pressing the test/reset switch for

two seconds.

4. Verify that the controller’s Alarm LED turns off.

Dirty Controller Test

The dirty controller test checks the controller’s ability to

initiate a dirty sensor test and indicate its results.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
Pressing the controller’s test/reset switch for longer

than seven seconds will put the duct detector into the

alarm state and activate all automatic alarm responses.

CAUTION

!

Dirty Controller Test Procedure

1. Press the controller’s test/reset switch for two

seconds.

2. Verify that the controller’s Trouble LED flashes.

Dirty Sensor Test

The dirty sensor test provides an indication of the sensor’s

ability to compensate for gradual environmental changes.

A sensor that can no longer compensate for environmental

changes is considered 100% dirty and requires cleaning or

replacing. You must use a field provided SD--MAG test

magnet to initiate a sensor dirty test. The sensor’s Dirty

LED indicates the results of the dirty test as shown in

Table 2.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
Holding the test magnet against the sensor housing for

more than seven seconds will put the duct detector

into the alarm state and activate all automatic alarm

responses.

CAUTION

!

Table 2 – Dirty LED Test

FLASHES

DESCRIPTION

1

0---25% dirty. (Typical of a newly installed detector)

2

25---50% dirty

3

51---75% dirty

4

76---99% dirty

Dirty Sensor Test Procedure

1. Hold the test magnet where indicated on the side of

the sensor housing for two seconds.

2. Verify that the sensor’s Dirty LED flashes.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
Changing the dirty sensor test operation will put the

detector into the alarm state and activate all automatic

alarm responses. Before changing dirty sensor test

operation, disconnect all auxiliary equipment from the

controller and notify the proper authorities if

connected to a fire alarm system.

CAUTION

!

50TC

Advertising