Caution, Detector cleaning – Carrier 50TCA04-A07 User Manual

Page 18

Advertising
background image

18

Changing the Dirt Sensor Test

By default, sensor dirty test results are indicated by:

S

The sensor’s Dirty LED flashing.

S

The controller’s Trouble LED flashing.

S

The controller’s supervision relay contacts toggle.

The operation of a sensor’s dirty test can be changed so

that the controller’s supervision relay is not used to

indicate test results. When two detectors are connected to

a controller, sensor dirty test operation on both sensors

must be configured to operate in the same manner.
To Configure the Dirty Sensor Test Operation

1. Hold the test magnet where indicated on the side of

the sensor housing until the sensor’s Alarm LED turns

on and its Dirty LED flashes twice (approximately 60

seconds).

2. Reset the sensor by removing the test magnet then

holding it against the sensor housing again until the

sensor’s Alarm LED turns off (approximately 2

seconds).

Remote Station Test

The remote station alarm test checks a test/reset station’s

ability to initiate and indicate an alarm state.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
This test places the duct detector into the alarm state.

Unless part of the test, disconnect all auxiliary

equipment from the controller before performing the

test. If the duct detector is connected to a fire alarm

system,

notify

the

proper

authorities

before

performing the test.

CAUTION

!

SD--TRK4 Remote Alarm Test Procedure

1. Turn the key switch to the RESET/TEST position for

seven seconds.

2. Verify that the test/reset station’s Alarm LED turns

on.

3. Reset the sensor by turning the key switch to the

RESET/TEST position for two seconds.

4. Verify that the test/reset station’s Alarm LED turns

off.

Remote Test/Reset Station Dirty Sensor Test

The test/reset station dirty sensor test checks the test/reset

station’s ability to initiate a sensor dirty test and indicate

the results. It must be wired to the controller as shown in

Fig. 24 and configured to operate the controller’s

supervision relay. For more information, see “Changing

sensor dirty test operation.”

1

12

14

13

19

15

2

20

3

Reset/Test

Trouble

Power

Alarm

Supervision relay
contacts [3]

5

4

1

3

2

SD-TRK4

2

1

TB3

18 Vdc ( )

+

18 Vdc ( )

Auxiliary

equipment

+

Wire must be

added by installer

Smoke Detector Controller

C08247

Fig. 24 -- Remote Test/Reset Station Connections

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
If the test/reset station’s key switch is left in the

RESET/TEST position for longer than seven seconds,

the detector will automatically go into the alarm state

and activate all automatic alarm responses.

CAUTION

!

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
Holding the test magnet to the target area for longer

than seven seconds will put the detector into the alarm

state and activate all automatic alarm responses.

CAUTION

!

Dirty Sensor Test Using an SD--TRK4

1. Turn the key switch to the RESET/TEST position for

two seconds.

2. Verify that the test/reset station’s Trouble LED

flashes.

DETECTOR CLEANING

Cleaning the Smoke Detector

Clean the duct smoke sensor when the Dirty LED is

flashing continuously or sooner if conditions warrant.