Carrier 50TCA04-A07 User Manual

Page 25

Advertising
background image

25

Table 5 – Thermistor Resistance vs Temperature

Values for Space Temperature Sensor, Supply Air

Temperature Sensor, and Outdoor Air Temperature

Sensor

TEMP

(C)

TEMP

(F)

RESISTANCE

(Ohms)

---40

---40

335,651

---35

---31

242,195

---30

---22

176,683

---25

---13

130,243

---20

---4

96,974

---15

5

72,895

---10

14

55,298

---5

23

42,315

0

32

32,651

5

41

25,395

10

50

19,903

15

59

15,714

20

68

12,494

25

77

10,000

30

86

8,056

35

95

6,530

40

104

5,325

45

113

4,367

50

122

3,601

55

131

2,985

60

140

2,487

65

149

2,082

70

158

1,752

NOTE: The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
Outdoor Air Temperature (OAT) Sensor — The OAT is

factory--mounted in the Economizer 2 (FIOP or

accessory). It is a nominal 10k ohm thermistor attached to

an

eyelet

mounting

ring.

See

Table

5

for

temperature--resistance characteristic.

Economizer 2 — The PremierLink control is used with

Economizer 2 (option or accessory) for outdoor air

management. The damper position is controlled directly

by the PremierLink control; Economizer 2 has no internal

logic device.

Outdoor air management functions can be enhanced with

field--installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors)
Space CO2 sensor
Outdoor air CO2 sensor

Refer to Table 6 for accessory part numbers

Field connections — Field connections for accessory

sensor and input devices are made at the 16--pole terminal

block (TB1) located on the control box bottom shelf in

front of the PremierLink control. Some input devices also

require a 24--vac signal source; connect at LCTB terminal

R at “THERMOSTAT” connection strip for this signal

source. See connections figures on following pages for

field connection locations (and for continued connections

at the PremierLink board inputs).

Table 7 provides a summary of field connections for units

equipped with Space Sensor. Table 8 provides a summary

of field connections for units equipped with Space

Thermostat.

Space Sensors -- The PremierLink controller is

factory--shipped configured for Space Sensor Mode. A

Carrier T--55 or T--56 space sensor must be used. T--55

space temperature sensor provides a signal of space

temperature to the PremierLink control. T--56 provides

same space temperature signal plus it allows for

adjustment of space temperature setpoints from the face of

the sensor by the occupants. See Table 5 for temperature

versus resistance characteristic on the space sensors.

Connect T--55 -- See Fig. 36 for typical T--55 internal

connections. Connect the T--55 SEN terminals to TB1

terminals 1 and 3 (see Fig. 37).

2

3

4

5

6

1

SW1

SEN

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

C08201

Fig. 36 -- T--55 Space Temperature Sensor Wiring

SEN

J6-7

J6-6

1

3

TB1

PL

SEN

C08212

Fig. 37 -- PremierLink T55 Sensor

50TC

Advertising