Fig. 62 -- enthalpy changeover setpoints – Carrier 50TCA04-A07 User Manual

Page 36

Advertising
background image

36

CONTROL

CURVE

A
B
C
D

CONTROL POINT

APPROX.

deg. F (deg. C)

AT 50% RH

73 (23)
70 (21)
67 (19)
63 (17)

12

1

4

16

18

20

22

24

26

28

30

32

3

4

36

38

40

42

44

46

9

0

1

0

0

80

70

6

0

50

40

30

20

10

ENTHALPY BTU PER POUND DRY AIR

85

(29)

90

(32)

95

(35)

100

(38)

105

(41)

110

(43)

35

(2)

35

(2)

40

(4)

40

(4)

105

(41)

110

(43)

45

(7)

45

(7)

50

(10)

50

(10)

55

(13)

55

(13)

60

(16)

60

(16)

65

(18)

65

(18)

70

(21)

70

(21)

75

(24)

75

(24)

80

(27)

80

(27)

85

(29)

90

(32)

95

(35)

100

(38)

A

A

B

B

C

C

D

D

RELATIVE HUMIDITY (%)

HIGH LIMIT

CURVE

APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)

C06037

Fig. 62 -- Enthalpy Changeover Setpoints

TR1

24 Vac

COM

TR

24

Vac

HOT

1

2

3

4

5

EF

EF1

+

_

P1

T1

P

T

N

EXH

2V

10V

EXH

Set

Set

2V

10V

2V

10V

DCV

DCV

Free

Cool

B

C

A

D

SO+

SR+

SR

SO

AQ1

AQ

DCV

Min

Pos

Open

Max

N1

C06038

Fig. 63 -- EonoMi$er IV Control

Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV

controller uses two enthalpy sensors (HH57AC078 and

CRENTDIF004A00), one in the outside air and one in the

return air duct. The EconoMi$er IV controller compares

the outdoor air enthalpy to the return air enthalpy to

determine EconoMi$er IV use. The controller selects the

lower enthalpy air (return or outdoor) for cooling. For

example, when the outdoor air has a lower enthalpy than

the return air, the EconoMi$er IV opens to bring in

outdoor air for free cooling.
Replace the standard outside air dry bulb temperature

sensor with the accessory enthalpy sensor in the same

mounting location. (See Fig. 52.) Mount the return air

enthalpy sensor in the return air duct. (See Fig. 61.)

Wiring is provided in the EconoMi$er IV wiring harness.

(See Fig. 52.) The outdoor enthalpy changeover setpoint is

set with the outdoor enthalpy setpoint potentiometer on

the EconoMi$er IV controller. When using this mode of

changeover

control,

turn

the

enthalpy

setpoint

potentiometer fully clockwise to the D setting.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation

control based on the level of CO

2

measured in the space

or return air duct.
Mount the accessory IAQ sensor according to

manufacturer specifications. The IAQ sensor should be

wired to the AQ and AQ1 terminals of the controller.

Adjust the DCV potentiometers to correspond to the DCV

voltage output of the indoor air quality sensor at the

user-determined setpoint. (See Fig. 64.)

50TC

Advertising