Carrier 50TCA04-A07 User Manual

Page 7

Advertising
background image

7

6. Hold garden sprayer nozzle close to finned areas and

apply cleaner with a vertical, up--and--down motion.

Avoid spraying in horizontal pattern to minimize po-

tential for fin damage.

7. Ensure cleaner thoroughly penetrates deep into finned

areas.

8. Interior and exterior finned areas must be thoroughly

cleaned.

9. Finned surfaces should remain wet with cleaning

solution for 10 minutes.

10. Ensure surfaces are not allowed to dry before rinsing.

Reapplying cleaner as needed to ensure 10--minute

saturation is achieved.

11. Thoroughly rinse all surfaces with low velocity clean

water using downward rinsing motion of water spray

nozzle. Protect fins from damage from the spray

nozzle.

Evaporator Coil

Cleaning the Evaporator Coil

1. Turn unit power off. Install lockout tag. Remove

evaporator coil access panel.

2. If economizer or two--position damper is installed, re-

move economizer by disconnecting Molex plug and

removing mounting screws.

3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dish-

washer detergent in a pressurized spray canister. Wash

both sides of coil and flush with clean water. For best

results, back--flush toward return--air section to re-

move foreign material. Flush condensate pan after

completion.

5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.

Evaporator Coil Metering Devices
The metering devices are multiple fixed--bore devices

(Acutrolt) wedged into the horizontal outlet tubes from

the liquid header, located at the entrance to each

evaporator coil circuit path. These are non--adjustable.

Service requires replacing the entire liquid header

assembly.

To check for possible blockage of one or more of these

metering devices, disconnect the supply fan contactor

(IFC) coil, then start the compressor and observe the

frosting pattern on the face of the evaporator coil. A frost

pattern should develop uniformly across the face of the

coil starting at each horizontal header tube. Failure to

develop frost at an outlet tube can indicate a plugged or a

missing orifice.

Refrigerant System Pressure Access Ports

There are two access ports in the system -- on the suction

tube near the compressor and on the discharge tube near

the compressor. These are brass fittings with black plastic

caps. The hose connection fittings are standard 1/4 SAE

Male Flare couplings.

The brass fittings are two--piece High Flow valves, with a

receptacle base brazed to the tubing and an integral

spring--closed check valve core screwed into the base.

(See Fig. 11.) This check valve is permanently assembled

into this core body and cannot be serviced separately;

replace the entire core body if necessary. Service tools are

available from RCD that allow the replacement of the

check valve core without having to recover the entire

system refrigerant charge. Apply compressor refrigerant

oil to the check valve core’s bottom o--ring. Install the

fitting body with 96 +/ --10 in--lbs of torque; do not

overtighten.

PURONR (R--410A) REFRIGERANT

This unit is designed for use with Puron (R--410A)

refrigerant. Do not use any other refrigerant in this

system.

Puron (R--410A) is provided in pink (rose) colored

cylinders. These cylinders are available with and without

dip tubes; cylinders with dip tubes will have a label

indicating this feature. For a cylinder with a dip tube,

place the cylinder in the upright position (access valve at

the top) when removing liquid refrigerant for charging.

For a cylinder without a dip tube, invert the cylinder

(access valve on the bottom) when removing liquid

refrigerant.

Because Puron (R--410A) is a blend, it is strongly

recommended that refrigerant always be removed from

the cylinder as a liquid. Admit liquid refrigerant into the

system in the discharge line. If adding refrigerant into the

suction line, use a commercial metering/expansion device

at the gauge manifold; remove liquid from the cylinder,

pass it through the metering device at the gauge set and

then pass it into the suction line as a vapor. Do not remove

Puron (R--410A) from the cylinder as a vapor.

Refrigerant Charge

Amount of refrigerant charge is listed on the unit’s

nameplate. Refer to Carrier GTAC2--5 Charging,

Recovery, Recycling and Reclamation training manual

and the following procedures.

Unit panels must be in place when unit is operating during

the charging procedure.
No Charge
Use standard evacuating techniques. After evacuating

system, weigh in the specified amount of refrigerant.
Low--Charge Cooling
Using Cooling Charging Charts, Fig. 12, vary refrigerant

until the conditions of the appropriate chart are met. Note

the charging charts are different from type normally used.

Charts are based on charging the units to the correct

superheat for the various operating conditions. Accurate

pressure gauge and temperature sensing device are

required. Connect the pressure gauge to the service port

on the suction line. Mount the temperature sensing device

on the suction line and insulate it so that outdoor ambient

temperature does not affect the reading. Indoor--air cfm

must be within the normal operating range of the unit.

50TC

Advertising