Caution, Indicators – Carrier 50TCA04-A07 User Manual

Page 19

Advertising
background image

19

Table 3 – Detector Indicators

CONTROL OR INDICATOR

DESCRIPTION

Magnetic test/reset switch

Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in

the normal state.

Alarm LED

Indicates the sensor is in the alarm state.

Trouble LED

Indicates the sensor is in the trouble state.

Dirty LED

Indicates the amount of environmental compensation used by the sensor

(flashing continuously = 100%)

Power LED

Indicates the sensor is energized.

OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel

and authority concern.
If the smoke detector is connected to a fire alarm

system, first notify the proper authorities that the

detector is undergoing maintenance then disable the

relevant circuit to avoid generating a false alarm.

CAUTION

!

1. Disconnect power from the duct detector then remove

the sensor’s cover. (See Fig. 25.)

2. Using a vacuum cleaner, clean compressed air, or a

soft bristle brush, remove loose dirt and debris from

inside the sensor housing and cover.

Use isopropyl alcohol and a lint--free cloth to remove

dirt and other contaminants from the gasket on the

sensor’s cover.

3. Squeeze the retainer clips on both sides of the optic

housing then lift the housing away from the printed

circuit board.

4. Gently remove dirt and debris from around the optic

plate and inside the optic housing.

5. Replace the optic housing and sensor cover.
6. Connect power to the duct detector then perform a

sensor alarm test.

Airflow

HVAC duct

Sampling

tube

Retainer
clip

Optic
plate

Optic
housing

Sensor
housing

C07305

Fig. 25 -- Sensor Cleaning Diagram

INDICATORS

Normal State

The smoke detector operates in the normal state in the

absence of any trouble conditions and when its sensing

chamber is free of smoke. In the normal state, the Power

LED on both the sensor and the controller are on and all

other LEDs are off.

Alarm State

The smoke detector enters the alarm state when the

amount of smoke particulate in the sensor’s sensing

chamber exceeds the alarm threshold value. (See Table 3.)

Upon entering the alarm state:

S

The sensor’s Alarm LED and the controller’s Alarm LED
turn on.

S

The contacts on the controller’s two auxiliary relays
switch positions.

S

The contacts on the controller’s alarm initiation relay
close.

S

The controller’s remote alarm LED output is activated
(turned on).

S

The controller’s high impedance multiple fan shutdown
control line is pulled to ground Trouble state.

The SuperDuct duct smoke detector enters the trouble

state under the following conditions:

S

A sensor’s cover is removed and 20 minutes pass before
it is properly secured.

S

A sensor’s environmental compensation limit is reached
(100% dirty).

S

A wiring fault between a sensor and the controller is
detected.

An internal sensor fault is detected upon entering the

trouble state:

S

The contacts on the controller’s supervisory relay switch
positions. (See Fig. 26.)

S

If a sensor trouble, the sensor’s Trouble LED the
controller’s Trouble LED turn on.

S

If 100% dirty, the sensor’s Dirty LED turns on and the
controller’s Trouble LED flashes continuously.

50TC

Advertising