Carrier 50TCA04-A07 User Manual

Page 30

Advertising
background image

30

SEN

J5-5

J5-6

COM

9

7

TB1

TB1

IAQ Sensor

PL

24 VAC

C08274

Fig. 44 -- Indoor CO2 Sensor (33ZCSENCO2) Connec-

tions

Refer to Form 33CS--58SI, PremierLink Installation,

Start--up, and Configuration Instructions, for detailed

configuration information

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus

weatherproof enclosure) — The outdoor air CO2 sensor is

designed to monitor carbon dioxide (CO2) levels in the

outside ventilation air and interface with the ventilation

damper in an HVAC system. The OAQ sensor is packaged

with an outdoor cover. See Fig. 45. The outdoor air CO2

sensor must be located in the economizer outside air hood.

COVER REMOVED

SIDE VIEW

C07135

Fig. 45 -- Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO2 Sensor — A dedicated

power supply is required for this sensor. A two--wire cable

is required to wire the dedicated power supply for the

sensor. The two wires should be connected to the power

supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

OAQ sensor. See Fig. 43. Connect the 4 to 20 mA

terminal to 50TC’s terminal TB1--11. Connect the SIG

COM terminal to 50TC’s terminal TB1--13. See Fig. 461.

SEN

J5-2

J5-3

COM

13

11

TB1

TB1

PL

OAQ Sensor/RH Sensor

24 VAC

C08275

Fig. 46 -- Outdoor CO2 Sensor Connections

Refer to Form 33CS--58SI, PremierLink Installation,

Start--up, and Configuration Instructions, for detailed

configuration information.

Smoke Detector/Fire Shutdown (FSD) — This function is

available only when PremierLink is configured for

(Space) Sensor Mode. The unit is factory--wired for

PremierLink FSD operation when PremierLink is

factory--installed.

On 50TC units equipped with factory--installed Smoke

Detector(s), the smoke detector controller implements the

unit shutdown through its NC contact set connected to the

unit’s LCTB input. The FSD function is initiated via the

smoke detector’s Alarm NO contact set. The PremierLink

communicates the smoke detector’s tripped status to the

CCN building control. See Fig. 23 for unit smoke detector

wiring.

Alarm state is reset when the smoke detector alarm

condition is cleared and reset at the smoke detector in the

unit.

If the PremierLink mode has been changed to Thermostat,

disconnect the BLU lead (from LCTB DDC--1) at TB1--6

(Y2) and tape off before connecting the thermostat to

TB1.

Filter Status Switch — This function is available only

when PremierLink is configured for (Space) Sensor Mode.

PremierLink control can monitor return filter status in two

ways: By monitoring a field--supplied/installed filter

pressure switch or via supply fan runtime hours.

Using switch input: Install the dirty filter pressure switch

according to switch manufacturer’s instructions, to

measure pressure drop across the unit’s return filters.

Connect one side of the switch’s NO contact set to

LCTB’s THERMOSTAT--R terminal. Connect the other

side of the NO contact set to TB1--10. Setpoint for Dirty

Filter is set at the switch. See Fig. 47.

R

10

TB1

LCTB
Thermostat

J4-4

PL

Filter Switch (NO, close on rising pressure (high drop))

C08216

Fig. 47 -- PremierLink Filter Switch Connection

When the filter switch’s NO contact set closes as filter

pressure drop increases (indicating dirt--laden filters), the

input signal to PremierLink causes the filter status point to

read “DIRTY”.

Using Filter Timer Hours: Refer to Form 33CS--58SI for

instructions on using the PremierLink Configuration

screens and on unit alarm sequence.

Supply Fan Status Switch — The PremierLink control can

monitor

supply

fan

operation

through

a

field--supplied/installed differential pressure switch. This

50TC

Advertising