Carrier 50TCA04-A07 User Manual

Page 42

Advertising
background image

42

Use the Carrier network communication software to start

up and configure the PremierLink controller.

Changes can be made using the ComfortWORKSr

software, ComfortVIEWt software, Network Service

Tool, System Pilott device, or Touch Pilott device. The

System Pilot and Touch Pilot are portable interface

devices that allow the user to change system set--up and

setpoints from a zone sensor or terminal control module.

During start--up, the Carrier software can also be used to

verify communication with Premier--Link controller.
NOTE: All set--up and setpoint configurations are factory
set and field--adjustable.
For specific operating instructions, refer to the literature

provided with user interface software.

Perform System Check--Out

1. Check correctness and tightness of all power and

communication connections.

2. At the unit, check fan and system controls for proper

operation.

3. At the unit, check electrical system and connections

of any accessory electric heater.

4. Check to be sure the area around the unit is clear of

construction dirt and debris.

5. Check that final filters are installed in the unit. Dust

and debris can adversely affect system operation.

6. Verify that the PremierLink controls are properly con-

nected to the CCN bus.

Initial Operation and Test

Perform the following procedure:

1. Apply 24 vac power to the control.
2. Connect the service tool to the phone jack service

port of the controller.

3. Using the Service Tool, upload the controller from

address 0, 31 at 9600 baud rate. The address may be

set at this time. Make sure that Service Tool is con-

nected to only one unit when changing the address.

Memory Reset
DIP switch 4 causes an E--squared memory reset to

factory defaults after the switch has been moved from

position 0 to position 1 and the power has been restored.

To enable the feature again, the switch must be put back

to the 0 position and power must be restored; this prevents

subsequent resets to factory defaults if the switch is left at

position 1.

To cause a reset of the non--volatile memory (to factory

defaults), turn the controller power off if it is on, move the

switch from position 1 to position 0, and then apply power

to the controller for a minimum of 5 seconds. At this

point, no action occurs, but the controller is now ready for

the memory to reset. Remove power to the controller

again and move the switch from position 0 to position 1.

This time, when power is applied, the memory will reset

to factory defaults. The controller address will return to

bus 0 element 31, indicating that memory reset occurred.

Refer to Installation Instruction 33CS--58SI for full

discussion on configuring the PremierLink control system.

Operating Sequence, Base Unit Controls

COOLING, UNITS WITHOUT ECONOMIZER — When

thermostat calls for cooling, terminals G and Y1 are

energized.

The

indoor--fan

contactor

(IFC)

and

compressor contactor are energized and indoor--fan motor,

compressor, and outdoor fan starts. The outdoor fan motor

runs continuously while unit is cooling.

HEATING, UNITS WITHOUT ECONOMIZER — When

the thermostat calls for heating, terminal W1 will be

energized with 24v. The IFC and heater contactor no. 1

(HC1) are energized.

COOLING, UNITS WITH ECONOMI$ER IV — When

free cooling is not available, the compressors will be

controlled by the zone thermostat. When free cooling is

available, the outdoor--air damper is modulated by the

EconoMi$er IV control to provide a 50 to 55_F supply--air

temperature into the zone. As the supply--air temperature

fluctuates above 55 or below 50_F, the dampers will be

modulated (open or close) to bring the supply-- air

temperature back within the setpoint limits.

Integrated EconoMi$er IV operation on single stage units

requires a 2--stage thermostat (Y1 and Y2).

For EconoMi$er IV operation, there must be a thermostat

call for the fan (G). This will move the damper to its

minimum position during the occupied mode.

If the increase in cooling capacity causes the supply--air

temperature to drop below 45_F, then the outdoor--air

damper position will be fully closed. If the supply--air

temperature continues to fall, the outdoor--air damper will

close. Control returns to normal once the supply--air

temperature rises above 48_F. If optional power exhaust is

installed, as the outdoor--air damper opens and closes, the

power exhaust fans will be energized and deenergized.

If field--installed accessory CO2 sensors are connected to

the EconoMi$er IV control, a demand controlled

ventilation strategy will begin to operate. As the CO2

level in the zone increases above the CO2 setpoint, the

minimum position of the damper will be increased

proportionally. As the CO2 level decreases because of the

increase in fresh air, the outdoor--air damper will be

proportionally closed. Damper position will follow the

higher demand condition from DCV mode or free cooling

mode.

Damper movement from full closed to full open (or vice

versa) will take between 1--1/2 and 2--1/2 minutes.

If free cooling can be used as determined from the

appropriate changeover command (switch, dry bulb,

enthalpy curve, differential dry bulb, or differential

enthalpy), a call for cooling (Y1 closes at the thermostat)

will cause the control to modulate the dampers open to

maintain the supply air temperature setpoint at 50 to 55_F.

As the supply--air temperature drops below the setpoint

range of 50 to 55_F, the control will modulate the

50TC

Advertising