PINK

VIOLET

BLACK

BLUE

YELL

O

W

NOTE 1

NOTE 3

RUN

500 OHM
RESISTOR

50HJ540573

ACTUATOR

ASSEMBLY

RED

WHITE

ECONOMISER2 PLUG

DIRECT DRIVE

ACTUATOR

4-20mA SIGNAL

OAT SENSOR

4-20 mA
TO J9 ON
PremierLink
BOARD

24 VAC

TRANSFORMER
GROUND

NOTES:

1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen

sor or HH57A077 enthalpy sensor.

3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.

C08310

Fig. 55 -- EconoMi$er2 with 4 to 20 mA Control Wiring

Table 11 – EconoMi$er IV Input/Output Logic

INPUTS

OUTPUTS

Demand Control

Ventilation (DCV)

Enthalpy*

Y1

Y2

Compressor

N Terminal†

Outdoor

Return

Stage

1

Stage

2

Occupied

Unoccupied

Damper

Below set

(DCV LED Off)

High

(Free Cooling LED Off)

Low

On On

On

On

Minimum position

Closed

On Off

On

Off

Off Off

Off

Off

Low

(Free Cooling LED On)

High

On On

On

Off

Modulating** (between min.

position and full-open)

Modulating** (between

closed and full-open)

On Off

Off

Off

Off Off

Off

Off

Minimum position

Closed

Above set

(DCV LED On)

High

(Free Cooling LED Off)

Low

On On

On

On

Modulating†† (between min.

position and DCV

maximum)

Modulating†† (between

closed and DCV

maximum)

On Off

On

Off

Off Off

Off

Off

Low

(Free Cooling LED On)

High

On On

On

Off

Modulating***

Modulating†††

On Off

Off

Off

Off Off

Off

Off

*

For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.

Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).

** Modulation is based on the supply-air sensor signal.
†† Modulation is based on the DCV signal.
*** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV)

or fully open (supply-air signal).

††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully

open (supply-air signal).