Carrier 50TCA04-A07 User Manual

Page 43

Advertising
background image

43

outdoor--air dampers closed to maintain the proper

supply--air temperature.

HEATING, UNITS WITH ECONOMI$ER IV — When

the room temperature calls for heat, the heating controls

are energized as described in the Heating, Units Without

Economizer section.

ECONOMIZER IN OCCUPIED MODE — The

economizer logic will be energized when the unit IFC is

energized. The economizer damper will open to the

minimum position setting and remain open until the IFC is

de--energized.

ECONOMIZER IN UNOCCUPIED MODE — The

economizer damper will remain closed during Unoccupied

Mode periods.

Operating Sequence, PremierLink Control

THERMOSTAT MODE — If the PremierLink controller

is configured for Thermostat mode (TSTAT), it will

control only to the thermostat inputs on J4. These inputs

can be overridden through CCN communication via the

CV_TSTAT points display table. When in this mode, the

fire safety shutdown (FSD) input cannot be used, so any

fire/life safety shutdown must be physically wired to

disable the 24 vac control circuit to the unit.

Indoor Fan — The indoor fan output will be energized

whenever there is 24 vac present on the G input. The

indoor fan will be turned on without any delay and the

economizer damper will open to its minimum position if

the unit has a damper connected to the controller. This

will also occur if the Premier--Link controller has been

configured for electric heat or heat pump operation.

Cooling — For cooling operation, there must be 24 vac

present on G. When G is active, the PremierLink

controller will then determine if outdoor conditions are

suitable for economizer cooling when an economizer

damper is available. A valid OAT, SPT (CCN space

temperature) and SAT (supply air temperature) sensor

MUST be installed for proper economizer operation. It

recommended that an outdoor or differential enthalpy

sensor also be installed. If one is not present, then a

jumper is needed on the ENTH input on J4, which will

indicate that the enthalpy will always be low. Economizer

operation will be based only on outdoor air dry bulb

temperature. The conditions are suitable when: enthalpy is

low, OAT is less than OATL High Lockout for TSTAT,

and OAT is less than OATMAX, the high setpoint for free

cooling. The default for OATL is 65_F. The default for

OATMAX is 75_F.

When all of the above conditions are satisfied and all the

required sensors are installed, the PremierLink controller

will use the economizer for cooling. One of three different

control routines will be used depending on the

temperature of the outside air. The routines use a PID loop

to control the SAT to a supply air setpoint (SASP) based

on the error from setpoint (SASPSAT). The SASP is

determined by the routine.

If an economizer is not available or the conditions are not

met for the following economizer routines below, the

compressors 1 and 2 will be cycled based on Y1 and Y2

inputs respectively.

Any time the compressors are running, the PremierLink

controller will lock out the compressors if the SAT

becomes too low. These user configurable settings are

found in the SERVICE configuration table:

Compressor 1 Lockout at SAT < SATLO1 (50 to 65_F)

(default is 55_F)

Compressor 2 Lockout at SAT < SATLO2 (45 to 55_F)

(default is 50_F)

After a compressor is locked out, it may be started again

after a normal time--guard period and the supply--air

temperature has increased at least 8_F above the lockout

setpoint.

Routine No. 1: If the OAT ≤ DXLOCK (OAT DX lockout

temperature) and DX Cooling Lockout is enabled when

Y1 input is energized, the economizer will be modulated

to maintain SAT at the Supply Air Setpoint (SASP) =

SATLO1 + 3_F (Supply Air Low Temp lockout for

compressor 1). When Y2 is energized, the economizer

will be modulated to control to a lower SASP = SATLO2

+ 3_F (Supply Air Low Temp lockout for compressor no.

2). Mechanical cooling is locked out and will not be

energized.

Routine No. 2: If DXLOCK (or DX Cooling Lockout is

disabled) < OAT ≤ 68_F when Y1 input is energized, the

economizer will be modulated to maintain SAT at SASP =

SATLO1 + 3_F. If the SAT > SASP + 5_F and the

economizer position > 85% then the economizer will

close the to minimum position for three minutes or until

the SAT > 68_F. The economizer integrator will then be

reset and begin modulating to maintain the SASP after

stage one has been energized for 90 seconds.

When Y2 is energized, the economizer will be modulated

to control to a lower supply air setpoint SASP= SATLO2

+ 3_F If the SAT > SASP + 5_F it will close the

economizer to minimum position for 3 minutes, reset the

integrator for the economizer, then start modulating the

economizer to maintain the SASP after the stage two has

been on for 90 seconds. This provides protection for the

compressor against flooded starts and allow refrigerant

flow to stabilize before modulating the economizer again.

By using return air across the evaporator coil just after the

compressor has started allows for increased refrigerant

flow rates providing better oil return of any oil washed out

during compressor start--up.

Routine No. 3: If the OAT > 68_F and the enthalpy is low

and the OAT <SPT then the economizer will open to

100% and compressors 1 and 2 will be cycled based on

Y1 and Y2 inputs respectively. If any of these conditions

are not met the economizer will go to minimum position.

If there is no call for heating or cooling, the economizer,

if available, will maintain the SASP at 70_F.

Heating — For gas or electric heat, HS1 and HS2 outputs

will follow W1 and W2 inputs respectively. The fan will

also be turned on if it is configured for electric heat.

50TC

Advertising