Economizer systems, Fig. 51 -- premierlink ccn bus connections, Fig. 52 -- economi$er iv component locations – Carrier 50TCA04-A07 User Manual

Page 32: Fig. 53 -- economi$er2 component locations, Fig. 54 -- economi$er iv wiring 50tc

Advertising
background image

32

(typically WHT) to the unit’s TB1--14 terminal. Connect

the CCN (--) lead (typically BLK) to the unit’s TB1--16

terminal. See Fig. 51.

CCN Bus

J2-1

J2-2

GND (WHT)

12

14

TB1

J2-3

– (BLK)

16

TB1

TB1

PL

+ (RED)

C08276

Fig. 51 -- PremierLink CCN Bus Connections

ECONOMIZER SYSTEMS

The 50TC units may be equipped with a factory--installed

or accessory (field--installed) economizer system. Two

types are available: with a logic control system

(EconoMi$er IV) and without a control system

(EconoMi$er2, for use with external control systems such

as PremierLink). See Fig. 52 and 53 for component

locations on each type. See Fig. 54 and 55 for economizer

section wiring diagrams.

Both economizers use direct--drive damper actuators.

ECONOMI$ER IV

CONTROLLER

OUTSIDE AIR

TEMPERATURE SENSOR

LOW AMBIENT

SENSOR

ACTUATOR

WIRING

HARNESS

C06021

Fig. 52 -- EconoMi$er IV Component Locations

ECONOMI$ER2

PLUG

BAROMETRIC

RELIEF

DAMPER

OUTDOOR

AIR HOOD

HOOD

SHIPPING

BRACKET

GEAR DRIVEN

DAMPER

C06022

Fig. 53 -- EconoMi$er2 Component Locations

FOR OCCUPANCY CONTROL

REPLACE JUMPER WITH

FIELD-SUPPLIED TIME CLOCK

LEGEND

DCV— Demand Controlled Ventilation

IAQ — Indoor Air Quality

LA — Low Ambient Lockout Device

OAT — Outdoor-Air Temperature

POT — Potentiometer

RAT — Return-Air Temperature

Potentiometer Defaults Settings:

Power Exhaust Middle

Minimum Pos.

Fully Closed

DCV Max.

Middle

DCV Set

Middle

Enthalpy

C Setting

NOTES:

1. 620 ohm, 1 watt 5% resistor should be removed only when using differential

enthalpy or dry bulb.

2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power

supply, it cannot have the secondary of the transformer grounded.

3. For field-installed remote minimum position POT, remove black wire jumper

between P and P1 and set control minimum position POT to the minimum

position.

8

7

C06028

Fig. 54 -- EconoMi$er IV Wiring

50TC