Warning – Carrier 50TCA04-A07 User Manual

Page 2

Advertising
background image

2

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal

injury or death.
Units with convenience outlet circuits may use

multiple disconnects. Check convenience outlet for

power status before opening unit for service. Locate

its disconnect switch, if appropriate, and open it.

Tag--out this switch, if necessary.

!

WARNING

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal

injury, death and/or equipment damage.
Puron (R--410A) refrigerant systems operate at higher

pressures than standard R--22 systems. Do not use

R--22 service equipment or components on Puron

refrigerant equipment.

!

WARNING

UNIT ARRANGEMENT AND ACCESS

General

Fig. 1 and 2 show general unit arrangement and access

locations.

FILTER ACCESS PANEL

OUTDOOR-AIR OPENING AND

INDOOR COIL ACCESS PANEL

COMPRESSOR

ACCESS PANEL

C06023

Fig. 1 -- Typical Access Panel Locations

BLOWER
ACCESS
PANEL

C07081

Fig. 2 -- Blower Access Panel Location

Routine Maintenance

These items should be part of a routine maintenance

program, to be checked every month or two, until a

specific schedule for each can be identified for this

installation:
Quarterly Inspection (and 30 days after initial start)

S

Return air filter replacement

S

Outdoor hood inlet filters cleaned

S

Belt tension checked

S

Belt condition checked

S

Pulley alignment checked

S

Fan shaft bearing locking collar tightness checked

S

Condenser coil cleanliness checked

S

Condensate drain checked

Seasonal Maintenance

These items should be checked at the beginning of each

season (or more often if local conditions and usage

patterns dictate):
Air Conditioning

S

Condenser fan motor mounting bolts tightness

S

Compressor mounting bolts

S

Condenser fan blade positioning

S

Control box cleanliness and wiring condition

S

Wire terminal tightness

S

Refrigerant charge level

S

Evaporator coil cleaning

S

Evaporator blower motor amperage

Heating

S

Power wire connections

S

Fuses ready

S

Manual--reset limit switch is closed

Economizer or Outside Air Damper

S

Inlet filters condition

S

Check damper travel (economizer)

S

Check gear and dampers for debris and dirt

Air Filters and Screens
Each unit is equipped with return air filters. If the unit has

an economizer, it will also have an outside air screen. If a

manual outside air damper is added, an inlet air screen

will also be present.

Each of these filters and screens will need to be

periodically replaced or cleaned.
Return Air Filters
Return air filters are disposable fiberglass media type.

Access to the filters is through the small lift--out panel