To Use Cooling Charging Charts
Take the outdoor ambient temperature and read the

suction pressure gauge. Refer to chart to determine what

suction temperature should be. If suction temperature is

high, add refrigerant. If suction temperature is low,

carefully recover some of the charge. Recheck the suction

pressure as charge is adjusted.

EXAMPLE:
Model 50TC*A06
Outdoor Temperature

85_F (29_C)

. . . . . . . . . . . . . . . . . .

Suction Pressure

130 psig (896 kPa)

. . . . . . . . . . . . . . . . .

Suction Temperature should be

63_F (17.2_C)

. . . . . . . . .

1/2-20 UNF RH

30

0.596

.47

5/8” HEX

SEAT

CORE

WASHER

DEPRESSOR PER ARI 720

+.01/-.035

FROM FACE OF BODY

7/16-20 UNF RH

O-RING

45

torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.

1/2" HEX

This surface provides a metal to metal seal when

o

o

C07150

Fig. 11 -- CoreMax Access Port Assembly

50TC