Carrier 50TCA04-A07 User Manual

Page 31

Advertising
background image

31

sequence will prevent (or interrupt) operation of unit

cooling, heating and economizer functions until the

pressure switch contacts are closed indicating proper

supply fan operation.

Install the differential pressure switch in the supply fan

section according to switch manufacturer’s instructions.

Arrange the switch contact to be open on no flow and to

close as pressure rises indicating fan operation.

Connect one side of the switch’s NO contact set to

LCTB’s THERMOSTAT--R terminal. Connect the other

side of the NO contact set to TB1--8. Setpoint for Supply

Fan Status is set at the switch. See Fig. 48

R

8

TB1

LCTB
Thermostat

J4-6

PL

Fan (Pressure) Switch (NO, close on rise in pressure)

C08118

Fig. 48 -- PremierLink Wiring Fan Pressure Switch

Connection

Remote Occupied Switch — The PremierLink control

permits a remote timeclock to override the control’s

on--board occupancy schedule and place the unit into

Occupied mode. This function may also provide a “Door

Switch” time delay function that will terminate cooling

and heating functions after a 2--20 minute delay.

Connect one side of the NO contact set on the timeclock

to LCTB’s THERMOSTAT--R terminal. Connect the other

side of the timeclock contact to the unit’s TB1--2 terminal.

J4-12

R

2

TB1

LCTB
Thermostat

PL

Time Clock

Remote Occupied

C08214

Fig. 49 -- PremierLink Wiring Remote Occupied

Refer to Form 33CS--58SI for additional information on

configuring the PremierLink control for Door Switch

timer function.

Power Exhaust (output) -- Connect the accessory Power

Exhaust contactor coils(s) per Fig. 50.

Power Exhaust

J8-3

15

C

TB1

THERMOSTAT

PL

PEC

TAN

GRA

LCTB

C08120

Fig. 50 -- PremierLink Power Exhaust Output

Connection

Space Relative Humidity Sensor — The RH sensor is not

used with 50TC models at this time.

CCN Communication Bus — The PremierLink controller

connects to the bus in a daisy chain arrangement.

Negative pins on each component must be connected to

respective negative pins, and likewise, positive pins on

each component must be connected to respective positive

pins. The controller signal pins must be wired to the signal

ground pins. Wiring connections for CCN must be made

at the 3--pin plug.

At any baud (9600, 19200, 38400 baud), the number of

controllers is limited to 239 devices maximum. Bus length

may not exceed 4000 ft, with no more than 60 total

devices on any 1000--ft section. Optically isolated RS--485

repeaters are required every 1000 ft.
NOTE: Carrier device default is 9600 band.
COMMUNICATION BUS WIRE SPECIFICATIONS —

The CCN Communication Bus wiring is field--supplied

and field--installed. It consists of shielded 3--conductor

cable with drain (ground) wire. The cable selected must

be identical to the CCN Communication Bus wire used for

the entire network.

See Table 9 for recommended cable.

Table 9 – Recommended Cables

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

NOTE: Conductors and drain wire must be at least 20
AWG, stranded, and tinned copper. Individual conductors
must be insulated with PVC, PVC/nylon, vinyl, Teflon, or
polyethylene. An aluminum/polyester 100% foil shield
and an outer jacket of PVC, PVC/nylon, chrome vinyl, or
Teflon with a minimum operating temperature range of

--20 C to 60 C is required. Do not run communication wire
in the same conduit as or next to any AC voltage wiring.
The communication bus shields must be tied together at

each system element. If the communication bus is entirely

within one building, the resulting continuous shield must

be connected to ground at only one single point. If the

communication bus cable exits from one building and

enters another building, the shields must be connected to

the grounds at a lightning suppressor in each building (one

point only).

Connecting CCN bus:
NOTE: When connecting the communication bus cable,
a color code system for the entire network is
recommended to simplify installation and checkout. See
Table 10 for the recommended color code.

Table 10 – Color Code Recommendations

SIGNAL TYPE

CCN BUS WIRE

COLOR

CCN PLUG PIN

NUMBER

+

Red

1

Ground

White

2

---

Black

3

Connect the CCN (+) lead (typically RED) to the unit’s

TB1--12 terminal. Connect the CCN (ground) lead