Caution – Carrier 50TCA04-A07 User Manual

Page 6

Advertising
background image

6

Two--Row Coils
Clean coil as follows:

1. Turn off unit power, tag disconnect.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 8. To

hold top panel open, place coil corner post between

top panel and center post. See Fig. 9.

C08205

Fig. 8 -- Cleaning Condenser Coil

C08206

Fig. 9 -- Propping Up Top Panel

4. Remove screws securing coil to compressor plate and

compressor access panel.

5. Remove fastener holding coil sections together at re-

turn end of condenser coil. Carefully separate the out-

er coil section 3 to 4 in. from the inner coil section.

See Fig. 10.

C08207

Fig. 10 -- Separating Coil Sections

6. Use a water hose or other suitable equipment to flush

down between the 2 coil sections to remove dirt and

debris. Clean the outer surfaces with a stiff brush in

the normal manner.

7. Secure inner and outer coil rows together with a

field--supplied fastener.

8. Reposition the outer coil section and remove the coil

corner post from between the top panel and center

post. Reinstall the coil corner post and replace all

screws.

Totaline Environmentally Sound Coil Cleaner

Application Equipment

S

2--1/2 gallon garden sprayer

S

Water rinse with low velocity spray nozzle

UNIT DAMAGE HAZARD
Failure to follow this caution may result in accelerated

corrosion of unit parts.
Harsh chemicals, household bleach or acid or basic

cleaners should not be used to clean outdoor or indoor

coils of any kind. These cleaners can be very difficult

to rinse out of the coil and can accelerate corrosion at

the fin/tube interface where dissimilar materials are in

contact. If there is dirt below the surface of the coil,

use the Totaline environmentally sound coil cleaner.

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced

unit performance or unit shutdown.
High velocity water from a pressure washer, garden

hose, or compressed air should never be used to

clean a coil. The force of the water or air jet will

bend the fin edges and increase airside pressure drop.

CAUTION

!

Totaline Environmentally Sound Coil Cleaner

Application Instructions

1. Proper eye protection such as safety glasses is recom-

mended during mixing and application.

2. Remove all surface loaded fibers and dirt with a vacu-

um

cleaner as described above.

3. Thoroughly wet finned surfaces with clean water and

a low velocity garden hose, being careful not to bend

fins.

4. Mix Totaline environmentally sound coil cleaner in a

2--1/2 gallon garden sprayer according to the instruc-

tions included with the cleaner. The optimum solution

temperature is 100_F.

NOTE: Do NOT USE water in excess of 130_F, as the
enzymatic activity will be destroyed.

5. Thoroughly apply Totaline environmentally sound

coil cleaner solution to all coil surfaces including

finned area, tube sheets and coil headers.

50TC

Advertising