Carrier 50TCA04-A07 User Manual

Page 37

Advertising
background image

37

0

1000

2000

3000

4000

5000

6000

2

3

4

5

6

7

8

800 ppm
900 ppm
1000 ppm
1100 ppm

RANGE

CONFIGURA

TION

(ppm)

DAMPER VOLTAGE FOR MAX VENTILATION RATE

CO SENSOR MAX RANGE SETTING

2

C06039

Fig. 64 -- CO2 Sensor Maximum Range Settings

If a separate field-supplied transformer is used to power

the IAQ sensor, the sensor must not be grounded or the

EconoMi$er IV control board will be damaged.
When using demand ventilation, the minimum damper

position represents the minimum ventilation position for

VOC

(volatile

organic

compounds)

ventilation

requirements. The maximum demand ventilation position

is used for fully occupied ventilation.
When demand ventilation control is not being used, the

minimum position potentiometer should be used to set the

occupied ventilation position. The maximum demand

ventilation position should be turned fully clockwise.
Exhaust Setpoint Adjustment
The exhaust setpoint will determine when the exhaust fan

runs based on damper position (if accessory power

exhaust is installed). The setpoint is modified with the

Exhaust Fan Setpoint (EXH SET) potentiometer. (See Fig.

58.) The setpoint represents the damper position above

which the exhaust fans will be turned on. When there is a

call for exhaust, the EconoMi$er IV controller provides a

45 ± 15 second delay before exhaust fan activation to

allow the dampers to open. This delay allows the damper

to reach the appropriate position to avoid unnecessary fan

overload.
Minimum Position Control
There is a minimum damper position potentiometer on the

EconoMi$er IV controller. (See Fig. 58.) The minimum

damper position maintains the minimum airflow into the

building during the occupied period.
When using demand ventilation, the minimum damper

position represents the minimum ventilation position for

VOC

(volatile

organic

compound)

ventilation

requirements. The maximum demand ventilation position

is used for fully occupied ventilation.
When demand ventilation control is not being used, the

minimum position potentiometer should be used to set the

occupied ventilation position. The maximum demand

ventilation position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the

minimum amount of outdoor air, as required by local

codes, to enter the building. Make minimum position

adjustments with at least 10_F temperature difference

between the outdoor and return-air temperatures.

To determine the minimum position setting, perform the

following procedure:

1. Calculate the appropriate mixed air temperature

using the following formula:

(T

O x

OA

) + (TR

x

RA

) =T

M

100

100

T

O

= Outdoor-Air Temperature

OA = Percent of Outdoor Air
T

R

= Return-Air Temperature

RA = Percent of Return Air
T

M

= Mixed-Air Temperature

As an example, if local codes require 10% outdoor

air

during

occupied

conditions,

outdoor-air

temperature is 60_ F, and return-air temperature is

75_F.
(60 x .10) + (75 x .90) = 73.5_F

2. Disconnect the supply air sensor from terminals T

and T1.

3. Ensure that the factory-installed jumper is in place

across terminals P and P1. If remote damper

positioning is being used, make sure that the

terminals are wired according to Fig. 52 and that the

minimum position potentiometer is turned fully

clockwise.

4. Connect 24 vac across terminals TR and TR1.
5. Carefully

adjust

the

minimum

position

potentiometer until the measured mixed air

temperature matches the calculated value.

6. Reconnect the supply air sensor to terminals T and

T1.

Remote control of the EconoMi$er IV damper is desirable

when requiring additional temporary ventilation. If a

field-supplied remote potentiometer (Honeywell part

number S963B1128) is wired to the EconoMi$er IV

controller, the minimum position of the damper can be

controlled from a remote location.
To control the minimum damper position remotely,

remove the factory-installed jumper on the P and P1

terminals on the EconoMi$er IV controller. Wire the

field-supplied potentiometer to the P and P1 terminals on

the EconoMi$er IV controller. (See Fig. 63.)
Damper Movement
Damper movement from full open to full closed (or vice

versa) takes 2

1

/

2

minutes.

Thermostats
The EconoMi$er IV control works with conventional

thermostats that have a Y1 (cool stage 1), Y2 (cool stage

2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The

EconoMi$er IV control does not support space

temperature sensors. Connections are made at the

thermostat terminal connection board located in the main

control box.
Occupancy Control
The factory default configuration for the EconoMi$er IV

control is occupied mode. Occupied status is provided by

the black jumper from terminal TR to terminal N. When

unoccupied mode is desired, install a field--supplied

50TC