Connect T--56 -- See Fig. 38 for T--56 internal

connections. Install a jumper between SEN and SET

terminals as illustrated. Connect T--56 terminals to TB1

terminals 1, 3 and 5 (see Fig. 39).

2

3

4

5

6

1

SW1

SEN

SET

Cool

Warm

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

JUMPER
TERMINALS
AS SHOWN

BLK
(T56)

C08202

Fig. 38 -- T--56 Internal Connections

SEN

J6-7

J6-6

1

3

TB1

PL

SEN

SET

Jumper

TB1

PL

J6-5

5

SET

C08213

Fig. 39 -- PremierLink T56 Sensor

Connect Thermostat — A 7--wire thermostat connection

requires a 24--v power source and a common connection.

Use the R and C terminals on the LCTB’s THERMOSTAT

connection strip for these. Connect the thermostat’s Y1,

Y2, W1, W2 and G terminals to PremierLink TB1 as

shown in Fig. 40.

If the 50TC unit is equipped with factory--installed smoke

detector(s), disconnect the factory BLU lead at TB1--6

(Y2) before connecting the thermostat. Identify the BLU

lead originating at LCTB DDC--1; disconnect at TB1--6

and tape off. Confirm that the second BLU lead at TB1--6

remains connected to PremierLink J4--8.

If the 50TC unit has an economizer system and

free--cooling operation is required, a sensor representing

Return Air Temperature must also be connected

(field--supplied and installed). This sensor may be a T--55

Space Sensor (see Fig. 36) installed in the space or in the

return duct, or it may be sensor PNO 33ZCSENSAT,

installed in the return duct. Connect this sensor to TB1--1

and TB1--3 per Fig.

37. Temperature--resistance

characteristic is found in Table 5.

Configure the unit for Thermostat Mode — Connect to the

CCN bus using a CCN service tool and navigate to

PremierLink Configuration screen for Operating Mode.

Default setting is Sensor Mode (value 1). Change the

value to 0 to reconfigure the controller for Thermostat

Mode.

When the PremierLink is configured for Thermostat

Mode, these functions are not available: Fire Shutdown

(FSD), Remote Occupied (RMTOCC), Compressor Safety

(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure

Switch (FILTER).

Economizer controls —

Outdoor Air Enthalpy Control (PNO HH57AC077) --

The enthalpy control (HH57AC077) is available as a

field--installed accessory to be used with the EconoMi$er2

damper system. The outdoor air enthalpy sensor is part of

the enthalpy control. (The separate field--installed

accessory return air enthalpy sensor (HH57AC078) is

required for differential enthalpy control. See below.)

Locate the enthalpy control in the economizer hood.

Locate two GRA leads in the factory harness and connect

these leads to enthalpy control sensors 2 and 3. See Fig.

41. Connect the enthalpy control power input terminals to

economizer actuator power leads RED (connect to TR)

and BLK (connect to TR).

G

J4-12

J4-10

J4-8

Y1

Y2

2

R

R

4

6

J4-6

J4-4

W2

C

8

10

C

SPACE
THERMOSTAT

PL

LCTB
THERMOSTAT

W1

TB1

LCTB
THERMOSTAT

C08119

Fig. 40 -- Space Thermostat Connections

6

7

LCTB
ECON

3

2

Enthalpy
Switch

GRA

GRA

Factory Wiring Harness

C08218

Fig. 41 -- Enthalpy Switch (HH57AC077) Connections

The outdoor enthalpy changeover setpoint is set at the

enthalpy controller.

50TC