Premierlink t control – Carrier 50TCA04-A07 User Manual

Page 23

Advertising
background image

23

C08199

Fig. 33 -- PremierLink Controller

PREMIERLINKT CONTROL

The PremierLink controller (see Fig. 33) is compatible

with Carrier Comfort Networkr (CCN) devices. This

control is designed to allow users the access and ability to

change factory--defined settings, thus expanding the

function of the standard unit control board. CCN service

access tools include System Pilot (TM), Touch Pilot (TM)

and Service Tool. (Standard tier display tools Navigatort

and Scrolling Marquee are not suitable for use with latest

PremierLink controller (Version 2.x).)

The PremierLink control is factory--mounted in the 50TC

unit’s main control box to the left of the LCTB. Factory

wiring is completed through harnesses connected to the

LVTB. Field connections are made at a 16--pole terminal

block (TB1) located on the bottom shelf of the unit

control box in front of the PremierLink controller The

factory--installed PremierLink control includes the

supply--air temperature (SAT) sensor. The outdoor air

temperature

(OAT)

sensor

is

included

in

the

FIOP/accessory Economizer 2 package.

Refer to Fig. 33 for PremierLink connection locations.
NOTE:

Refer to Form 33CS--58SI for complete

PremierLink configuration, operating sequences and
troubleshooting information. Have a copy of this manual

available at unit start--up.
The PremierLink controller requires the use of a Carrier

electronic thermostat or a CCN connection for time

broadcast to initiate its internal timeclock. This is

necessary for broadcast of time of day functions

(occupied/unoccupied).
NOTE:

PremierLink controller is shipped in Sensor

mode. To be used with a thermostat, the PremierLink
controller must be configured to Thermostat mode. Refer
to PremierLink Configuration instructions for Operating
Mode.

Supply

Air

Temperature

(SAT)

Sensor

On

FIOP--equipped 50TC unit, the unit is supplied with a

supply--air temperature (SAT) sensor (33ZCSENSAT).

This sensor is a tubular probe type, approx 6--inches (12.7

mm) in length. It is a nominal 10--k ohm thermistor. See

Table 15 for temperature--resistance characteristic.

The SAT is factory--wired. The SAT probe is wire--tied to

the supply--air opening (on the horizontal opening end) in

its shipping position. Remove the sensor for installation.

Re--position the sensor in the flange of the supply--air

opening or in the supply air duct (as required by local

codes). Drill or punch a 1/2--in. hole in the flange or duct.

Use two field--supplied, self--drilling screws to secure the

sensor probe in a horizontal orientation. See Fig. 36.

SUPPLY AIR

RETURN AIR

SUPPLY AIR
TEMPERATURE
SENSOR

ROOF
CURB

C08200

Fig. 34 -- Typical Mounting Location for Supply Air

Temperature (SAT) Sensor on Small Rooftop Units

50TC