5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode

to continue to the next variable.

Dehumidification of Fresh Air with DCV (Demand

Controlled Ventilation) Control
If normal rooftop heating and cooling operation is not

adequate for the outdoor humidity level, an energy

recovery unit and/or a dehumidification option should be

considered.
EconoMi$er IV Preparation
This procedure is used to prepare the EconoMi$er IV for

troubleshooting. No troubleshooting or testing is done by

performing the following procedure.
NOTE:

This procedure requires a 9--v battery, 1.2

kilo--ohm resistor, and a 5.6 kilo--ohm resistor which are
not supplied with the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all
potentiometers before starting troubleshooting.

1. Disconnect power at TR and TR1. All LEDs should

be off. Exhaust fan contacts should be open.

2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo--ohm

resistor across T and T1.

5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals SO and +.

Connect 1.2 kilo--ohm 4074EJM checkout resistor

across terminals SO and +.

8. Put 620--ohm resistor across terminals SR and +.
9. Set minimum position, DCV setpoint, and exhaust po-

tentiometers fully CCW (counterclockwise).

10. Set DCV maximum position potentiometer fully CW

(clockwise).

11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.

Differential Enthalpy
To check differential enthalpy:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Place 620--ohm resistor across SO and +.
3. Place 1.2 kilo--ohm resistor across SR and +. The

Free Cool LED should be lit.

4. Remove 620--ohm resistor across SO and +. The Free

Cool LED should turn off.

5. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

Single Enthalpy
To check single enthalpy:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Set the enthalpy potentiometer to A (fully CCW). The

Free Cool LED should be lit.

3. Set the enthalpy potentiometer to D (fully CW). The

Free Cool LED should turn off.

4. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

DCV (Demand Controlled Ventilation) and Power

Exhaust
To check DCV and Power Exhaust:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Ensure terminals AQ and AQ1 are open. The LED for

both DCV and Exhaust should be off. The actuator

should be fully closed.

3. Connect a 9--v battery to AQ (positive node) and AQ1

(negative node). The LED for both DCV and Exhaust

should turn on. The actuator should drive to between

90 and 95% open.

4. Turn the Exhaust potentiometer CW until the Exhaust

LED turns off. The LED should turn off when the po-

tentiometer is approximately 90%. The actuator

should remain in position.

5. Turn the DCV setpoint potentiometer CW until the

DCV LED turns off. The DCV LED should turn off

when the potentiometer is approximately 9--v. The ac-

tuator should drive fully closed.

6. Turn the DCV and Exhaust potentiometers CCW until

the Exhaust LED turns on. The exhaust contacts will

close 30 to 120 seconds after the Exhaust LED turns

on.

7. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

2. Connect a 9--v battery to AQ (positive node) and AQ1

(negative node). The DCV LED should turn on. The

actuator should drive to between 90 and 95% open.

3. Turn the DCV Maximum Position potentiometer to

midpoint. The actuator should drive to between 20

and 80% open.

4. Turn the DCV Maximum Position potentiometer to

fully CCW. The actuator should drive fully closed.

5. Turn the Minimum Position potentiometer to mid-

point. The actuator should drive to between 20 and

80% open.

6. Turn the Minimum Position Potentiometer fully CW.

The actuator should drive fully open.

7. Remove the jumper from TR and N. The actuator

should drive fully closed.

8. Return EconoMi$er IV settings and wiring to normal

after completing troubleshooting.

Supply--Air Sensor Input
To check supply--air sensor input:

1. Make sure EconoMi$er IV preparation procedure has

been performed.

50TC