Recommended sizing of 3 phase supply wires – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 10

Advertising
background image

10

EXCERPTS FROM NEC 2005 HANDBOOK - BASED ON NFPA 70

Partial Table 310.16 Allowable Ampacities of Insulated Conductors (0-2000 Volts)

- Not more then 3 current carrying conductors in cable or raceway

- Based on Ambient Temp of 30˚C

Copper Wire Only

How to Estimate Unit Supply Wire Requirements:

1.) Determine Nominal Input Voltage
2) Estimate Length of Wire from Breaker to Unit Disconnect
3) Find Unit MCA for desired confi guration
4) Using the minimum wire size based on the unit MCA, calculate

the % Voltage Drop to determine the initial wire gauge. The
%VD should be 3% or less at the unit

5) Verify Unit Voltage is within the Appliances min/max limits
6) Verify that the Wire ampacity (corrected for temperature &

number of conductors) is above the Appliances MCA

7) Based on fi nal wire gauge selection, determine conduit size.

Refer to NEC for details and allowable fi ll rate

8) Based on Appliance MOP and fi nal wire selection, make

selection of Appliance branch circuit protection

Size

Temperature Rating of

Conductor

Size

AWG or

kcmil

60˚C

75˚C

90˚C

AWG or

kcmil

14

20

20

25

14

12

25

25

30

12

10

30

35

40

10

8

40

50

55

8

6

55

65

75

6

4

70

85

95

4

3

85

100

110

3

2

95

115

130

2

1

110

130

150

1

1/0

125

150

170

1/0

2/0

145

175

195

2/0

3/0

165

200

225

3/0

Amb. Temperature Correction Factors

Amb.

Temp

(˚C)

Temperature Rating

of Conductor

Amb.

Temp

(˚F)

60˚C

75˚C

90˚C

21-25

1.08

1.05

1.04

70-77

26-30

1.00

1.00

1.00

78-86

31-35

0.91

0.94

0.96

87-95

36-40

0.82

0.88

0.91

96-104

41-45

0.71

0.82

0.87

105-113

46-50

0.58

0.75

0.82

114-122

51-55

0.41

0.67

0.76

123-131

# of Current-Carrying

Conductors

Amount to adjust values in

Table 310.16 after correction

for Ambient Temperature (if

necessary)

4 to 6
7 to 9

80%
70%

Partial Table 9 Effective Impedance for 600V Cables, 3Ø, 60 Hz, 75˚C - 3 single current-carrying conductors in conduit

Uncoated Copper Wire Only

Effective Impedance (Z) at 0.85 PF

to Neutral / 1000 ft

AWG or

kcmil

PVC

Conduit

Aluminum

Conduit

Steel

Conduit

14

2.7

2.7

2.7

12

1.7

1.7

1.7

10

1.1

1.1

1.1

8

0.69

0.69

0.70

6

0.44

0.45

0.45

4

0.29

0.29

0.30

3

0.23

0.24

0.24

2

0.19

0.19

0.20

1

0.16

0.16

0.16

1/0

0.13

0.13

0.13

2/0

0.11

0.11

0.11

3/0

0.088

0.092

0.094

The above tables and recommended procedures are provided for reference only. For complete details refer to the current version of
the National Electric Code, the applicable local codes & ordinances, or consult a qualifi ed professional.

100

%

3

1000

9

tage

NomLineVol

p

VoltageDro

p

VoltageDro

p

VoltageDro

p

VoltageDro

UnitMCA

ft

gth

CircuitLen

Value

Table

p

VoltageDro

Line

to

Line

Neutraul

to

Line

Line

to

Line

Neutraul

to

Line

Figure 9. Excerpts from NEC 2005 Handbook

RECOMMENDED SIZING OF 3 PHASE SUPPLY WIRES