Blower performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 27

Advertising
background image

27

R4GM & R6GN-150* Series

HSD kits:
918799 (208-230V, 3Ø, 60 Hz)
920637 (460V, 3Ø, 60 Hz)

Blower Performance Chart

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open ‡

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.9

CFM

RPM

kW

1.0

CFM

RPM

kW

1.1

CFM

5350

5100

4850

RPM

1188

1168

1148

kW

3.20

2.98

2.75

1.2

CFM

5225

5000

4700

4400

RPM

1210

1189

1169

1148

kW

3.23

3.00

2.75

2.50

1.3

CFM

5100

4850

4600

4250

3900

RPM

1231

1211

1190

1170

1149

kW

3.25

3.00

2.75

2.53

2.30

1.4

CFM

5300

5050

4800

4500

4200

RPM

1271

1252

1232

1212

1191

kW

3.55

3.33

3.10

2.85

2.60

1.5

CFM

5400

5150

4900

4650

4400

4050

3700

RPM

1313

1293

1273

1253

1233

1213

1192

kW

3.80

3.55

3.30

3.09

2.87

2.59

2.30

1.6

CFM

5375

5000

4725

4450

4175

3900

3600

RPM

1334

1314

1295

1275

1255

1235

1214

kW

3.90

3.60

3.35

3.10

2.86

2.62

2.35

1.7

CFM

5350

4925

4500

4250

4000

RPM

1355

1336

1316

1296

1276

kW

4.00

3.70

3.40

3.15

2.90

1.8

CFM

4850

4475

4100

3725

RPM

1357

1338

1318

1297

kW

3.75

3.48

3.20

2.95

1.9

CFM

4400

4000

3600

RPM

1359

1340

1320

kW

3.50

3.23

2.95

2.0

CFM

RPM

kW

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 23. Blower Performance for R4GM & R6GN-150* Units

(15 Ton Models Only)

Advertising