Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 24

Advertising
background image

24

P6SP-120* & Q6SP-120* & Q5SN-120*

HSD kits:
920395 (208-230V, 3Ø, 60 Hz)
920396 (460V, 3Ø, 60 Hz)

Horizontal Flow Performance Chart*

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open

2.0 Turns

Open

2.5 Turns

Open ‡

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.9

CFM

4904

4685

RPM

956.5

937

kW

2.81

2.58

1.0

CFM

4914

4717

4520

RPM

980

959

938

kW

2.94

2.7

2.46

1.1

CFM

4738

4527

4317

RPM

982

961

940

kW

2.8

2.57

2.34

1.2

CFM

4784

4561

4317

4073

RPM

1002.5

984

964

944

kW

2.94

2.66

2.43

2.19

1.3

CFM

4568

4378

4125

3871

RPM

1005.5

987

967

946

kW

2.79

2.53

2.29

2.04

1.4

CFM

4558

4352

4147

3897

3647

RPM

1027

1009

990

970

949

kW

2.90

2.65

2.40

2.16

1.93

1.5

CFM

4358

4137

3915

3595

RPM

1030

1012

993

973

kW

2.74

2.50

2.26

2.02

1.6

CFM

4326

4135

3749

3363

RPM

1052

1033

1016

999

kW

2.87

2.60

2.35

2.10

1.7

CFM

4327

4120

3912

3361

RPM

1072

1054

1036

1020

kW

2.96

2.71

2.46

2.20

1.8

CFM

4137

3889

3640

RPM

1074

1057

1040

kW

2.78

2.54

2.29

1.9

CFM

4068

3824

3313

RPM

1096

1077

1063

kW

2.87

2.60

2.26

2.0

CFM

4083

3797

3511

RPM

1118

1099

1080

kW

2.93

2.68

2.42

*

Requires horizontal conversion kit. Please refer to unit TSL for kit number.

Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 20. Blower Performance for P6SP-120*, Q6SP-120*, & Q5SN-120* Units

(10 Ton Horizontal Models Only)