R6GP-072*-166C

MSD kits:
920609 (208-230V, 3Ø, 60 Hz)
920560 (460V, 3Ø, 60 Hz)

Downfl ow Performance Chart

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open ‡

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.8

CFM

RPM

kW

0.9

CFM

2736

2468

2200

RPM

981

953

925

kW

1.22

1.04

0.85

1.0

CFM

2684

2443

2151

RPM

1009

985

956

kW

1.22

1.01

0.88

1.1

CFM

2632

2351

2070

RPM

1037

1013

988

kW

1.25

1.07

0.89

1.2

CFM

2589

2281

2143

RPM

1066

1041

1019

kW

1.32

1.12

0.98

1.3

CFM

2546

2321

2095

RPM

1098

1072

1046

kW

1.35

1.21

1.07

1.4

CFM

2591

2280

2157

RPM

1124

1102

1078

kW

1.41

1.25

1.10

1.5

CFM

2443

2365

2164

RPM

1157

1128

1108

kW

1.42

1.39

1.18

1.6

CFM

2502

2344

RPM

1186

1161

kW

1.52

1.35

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 13. Blower Performance for R6GP-072*-166C Units

(6 Ton Downfl ow Models Only)