Downfl ow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 29

Advertising
background image

29

R6GP-090*-200C

HSD kits:
920559 (208-230V, 3Ø, 60 Hz)
920558 (460V, 3Ø, 60 Hz)

Downfl ow Performance Chart

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open ‡

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

1.2

CFM

3417

3226

3035

RPM

1232

1203

1173

kW

2.32

2.10

1.88

1.3

CFM

3258

3055

2852

RPM

1235

1205

1175

kW

2.15

1.96

1.78

1.4

CFM

3448

3267

3085

2856

2626

RPM

1292

1265

1237

1208

1178

kW

2.47

2.24

2.01

1.82

1.64

1.5

CFM

3300

3099

2898

2677

RPM

1295

1268

1240

1211

kW

2.33

2.10

1.86

1.66

1.6

CFM

3164

2932

2705

RPM

1299

1271

1243

kW

2.24

1.96

1.69

1.7

CFM

3392

3178

2963

2756

RPM

1356

1329

1302

1274

kW

2.63

2.34

2.06

1.80

1.8

CFM

3422

3214

2997

RPM

1384

1358

1332

kW

2.75

2.53

2.26

1.9

CFM

3437

3251

3016

RPM

1414

1389

1364

kW

2.88

2.58

2.42

2.0

CFM

3306

3033

RPM

1419

1394

kW

2.76

2.45

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 25. Blower Performance for R6GP-090*-200C Units