Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 12

Advertising
background image

12

P6SP-072*

MSD kits:
920609 (208-230V, 3Ø, 60 Hz)
920560 (460V, 3Ø, 60 Hz)

Horizontal Flow Performance Chart*

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open ‡

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.8

CFM

RPM

kW

0.9

CFM

2716

2500

2284

RPM

985

956

926

kW

1.17

1.05

0.93

1.0

CFM

2677

2491

2250

RPM

1012

987

959

kW

1.23

1.09

0.94

1.1

CFM

2682

2469

2255

RPM

1039

1015

990

kW

1.29

1.13

0.98

1.2

CFM

2663

2452

RPM

1067

1041

kW

1.35

1.18

1.3

CFM

2710

2465

2219

RPM

1096

1071

1046

kW

1.45

1.26

1.07

1.4

CFM

2675

2492

RPM

1126

1100

kW

1.47

1.33

1.5

CFM

2487

2195

RPM

1133

1109

kW

1.37

1.17

1.6

CFM

2558

2208

RPM

1159

1137

kW

1.48

1.20

*

Requires horizontal conversion kit. Please refer to unit TSL for kit number.

Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 8. Blower Performance for P6SP-072* Units

(6 Ton Horizontal Models Only)