Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 16

Advertising
background image

16

R6GP-072*-100C

MSD kits:
920609 (208-230V, 3Ø, 60 Hz)
920560 (460V, 3Ø, 60 Hz)

Horizontal Flow Performance Chart*

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open ‡

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.8

CFM

RPM

kW

0.9

CFM

2618

2403

2188

RPM

975

948

920

kW

1.12

0.98

0.84

1.0

CFM

2577

2367

2073

1865

RPM

1006

980

952

924

kW

1.17

0.99

0.88

0.70

1.1

CFM

2562

2361

2085

RPM

1037

1006

983

kW

1.21

1.07

0.93

1.2

CFM

2575

2328

2085

RPM

1062

1041

1011

kW

1.31

1.10

0.95

1.3

CFM

2601

2356

2048

RPM

1094

1066

1045

kW

1.36

1.18

0.98

1.4

CFM

2580

2357

2126

RPM

1122

1099

1071

kW

1.46

1.25

1.12

1.5

CFM

2569

2323

2129

RPM

1149

1125

1104

kW

1.51

1.33

1.16

1.6

CFM

2307

RPM

1154

kW

1.37

*

Requires horizontal conversion kit. Please refer to unit TSL for kit number.

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 12. Blower Performance for R6GP-072* Units

(6 Ton Horizontal Models Only)