Downfl ow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 31

Advertising
background image

31

R6GP-120*-235C

HSD kits:
920395 (208-230V, 3Ø, 60 Hz)
920396 (460V, 3Ø, 60 Hz)

Downfl ow Performance Chart

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open ‡

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.9

CFM

RPM

kW

1.0

CFM

RPM

kW

1.1

CFM

4672

RPM

975

kW

2.65

1.2

CFM

4673

4466

RPM

998

979

kW

2.75

2.50

1.3

CFM

4630

4429

4227

RPM

1018

1000

982

kW

2.90

2.65

2.40

1.4

CFM

4611

4394

4191

3988

RPM

1039

1020

1003

985

kW

2.95

2.70

2.50

2.30

1.5

CFM

4613

4391

4168

3714

3260

RPM

1058

1041

1023

1006

989

kW

3.10

2.85

2.60

2.38

2.15

1.6

CFM

4379

4181

3982

3257

RPM

1061

1046

1031

1012

kW

2.90

2.70

2.50

2.25

1.7

CFM

4480

4233

3976

3718

RPM

1087

1070

1053

1036

kW

3.10

2.80

2.55

2.30

1.8

CFM

4244

3996

3683

3370

RPM

1089

1072

1056

1039

kW

2.90

2.60

2.40

2.20

1.9

CFM

4278

4011

3744

RPM

1111

1093

1075

kW

3.10

2.80

2.50

2.0

CFM

4252

4016

3455

RPM

1130

1115

1097

kW

3.10

2.90

2.50

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 27. Blower Performance for R6GP-120*-235C Units

(10 Ton Downfl ow Models Only)