13

P6SP-090*

MSD kits:
920607 (208-230V, 3Ø, 60 Hz)
920606 (460V, 3Ø, 60 Hz)

Downfl ow Performance Chart

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open ‡

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.8

CFM

3415

3252

3042

2831

RPM

1119

1088

1059

1030

kW

1.92

1.73

1.62

1.50

0.9

CFM

3442

3247

3052

2834

2615

RPM

1150

1121

1092

1063

1033

kW

2.03

1.82

1.62

1.53

1.43

1.0

CFM

3447

3256

3072

2887

2658

2428

RPM

1181

1153

1124

1095

1065

1035

kW

2.11

1.85

1.66

1.47

1.39

1.31

1.1

CFM

3286

3077

2849

2621

RPM

1185

1157

1127

1097

kW

2.00

1.75

1.57

1.39

1.2

CFM

3326

3074

2822

2598

RPM

1215

1189

1162

1133

kW

2.20

1.92

1.64

1.42

1.3

CFM

3320

3064

2856

2647

RPM

1248

1221

1192

1163

kW

2.22

1.92

1.72

1.51

1.4

CFM

3365

3126

2887

2643

RPM

1277

1251

1224

1197

kW

2.32

2.09

1.86

1.57

1.5

CFM

3127

2911

2695

RPM

1283

1255

1227

kW

2.15

1.94

1.73

1.6

CFM

3323

3151

2978

2751

RPM

1340

1313

1286

1259

kW

2.54

2.30

2.05

1.80

Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 9. Blower Performance for P6SP-090* Units

(7.5 Ton Downfl ow Models Only)

Advertising