R4GM & R6GN-180* Series

HSD kits:
918800 (208-230/460V, 3Ø, 60 Hz)

Blower Performance Chart

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open ‡

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.9

CFM

RPM

kW

1.0

CFM

RPM

kW

1.1

CFM

5800

5575

5350

5100

4850

RPM

1228

1208

1188

1168

1148

kW

3.65

3.43

3.20

2.98

2.75

1.2

CFM

6200

5850

5500

5250

5000

4700

4400

RPM

1270

1250

1230

1210

1189

1169

1148

kW

4.1

3.80

3.50

3.25

3.00

2.75

2.50

1.3

CFM

6100

5850

5600

5350

5100

4850

4600

RPM

1309

1290

1271

1251

1231

1211

1190

kW

4.25

4.03

3.80

3.55

3.30

3.03

2.75

1.4

CFM

5800

5550

5300

5050

4800

4500

4200

RPM

1310

1291

1272

1252

1232

1211.5

1191

kW

4.00

3.78

3.55

3.33

3.10

2.85

2.60

1.5

CFM

6000

5700

5400

5150

4900

4650

4400

RPM

1353

1333

1312

1293

1273

1253

1233

kW

4.45

4.13

3.80

3.55

3.30

3.09

2.87

1.6

CFM

5650

5325

5000

4725

4450

RPM

1354

1334

1314

1295

1275

kW

4.25

3.93

3.60

3.35

3.10

1.7

CFM

5350

4925

4500

RPM

1355

1336

1316

kW

4.00

3.70

3.40

1.8

CFM

4850

4475

4100

RPM

1357

1338

1318

kW

3.75

3.48

3.20

1.9

CFM

4400

RPM

1359

kW

3.50

2.0

CFM

RPM

kW

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 24. Blower Performance for R4GM & R6GN-180* Units

(15 Ton Models Only)