Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 26

Advertising
background image

26

Q6SP-090* & Q5SN-090*

HSD kits:
920394 (208-230V, 3Ø, 60 Hz)
920608 (460V, 3Ø, 60 Hz)

Horizontal Flow Performance Chart*

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open ‡

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.9

CFM

RPM

kW

1.0

CFM

RPM

kW

1.1

CFM

3890

RPM

891

kW

1.93

1.2

CFM

4140

3883

3625

RPM

937

915

893

kW

2.28

2.05

1.82

1.3

CFM

3910

3585

3260

RPM

939

918

897

kW

2.15

1.91

1.66

1.4

CFM

4150

3895

3640

RPM

983

963

942

kW

2.45

2.23

2.00

1.5

CFM

3940

3595

3250

RPM

985

965

945

kW

2.33

2.08

1.82

1.6

CFM

3630

RPM

988

kW

2.15

1.7

CFM

3960

3355

2750

RPM

1031

1014

996

kW

2.52

2.13

1.74

1.8

CFM

3690

RPM

1035

kW

2.35

1.9

CFM

3975

3388

2800

RPM

1073

1059

1044

kW

2.73

2.33

1.92

2.0

CFM

3059

RPM

1083

kW

2.22

*

Requires horizontal conversion kit. Please refer to unit TSL for kit number.

Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 22. Blower Performance for Q6SP-090* & Q5SN-090* Units

(7.5 Ton Horizontal Models Only)