P6SP-120* & Q6SP-120* & Q5SN-120*

HSD kits:
920396 (460V, 3Ø, 60 Hz)
920395 (208-230V, 3Ø, 60 Hz)

Downfl ow Performance Chart

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open

2.0 Turns

Open

2.5 Turns

Open ‡

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.9

CFM

4903

4734

4565

4370

4174

RPM

1020

1001

982

962

942

kW

3.01

2.82

2.62

2.42

2.23

1.0

CFM

4724

4561

4397

4185

3973

RPM

1023

1005

986

965

944

kW

2.90

2.72

2.54

2.34

2.14

1.1

CFM

4583

4385

4186

3970

3754

RPM

1026

1007

988

967

946

kW

2.80

2.60

2.40

2.21

2.03

1.2

CFM

4562

4368

4169

3969

3724

3479

RPM

1047

1029

1010

990

969

949

kW

2.92

2.69

2.49

2.29

2.08

1.87

1.3

CFM

4571

4366

4161

3942

3723

3477

RPM

1068

1050

1032

1012

993

972

kW

3.01

2.78

2.56

2.35

2.14

1.93

1.4

CFM

4387

4171

3954

3715

3476

RPM

1071

1053

1035

1015

995

kW

2.87

2.64

2.42

2.20

1.99

1.5

CFM

4354

4164

3960

3757

3493

RPM

1092

1075

1056

1037

1017

kW

3.00

2.74

2.52

2.30

2.07

1.6

CFM

4144

3941

3750

3559

RPM

1096

1078

1059

1039

kW

2.86

2.61

2.40

2.18

1.7

CFM

4119

3934

3749

3555

RPM

1117

1099

1081

1061

kW

2.96

2.72

2.49

2.28

1.8

CFM

4102

3891

3724

3556

RPM

1136

1121

1103

1084

kW

3.00

2.80

2.59

2.37

1.9

CFM

3886

3766

3565

RPM

1140

1123

1105

kW

2.89

2.74

2.50

2.0

CFM

3862

3762

3534

RPM

1159

1142

1126

kW

3.03

2.82

2.58

Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 19. Blower Performance for P6SP-120*, Q6SP-120*, & Q5SN-120* Units

(10 Ton Downfl ow Models Only)