Downfl ow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 19

Advertising
background image

19

R6GP-090*-200C

MSD kits:
920607 (208-230V, 3Ø, 60 Hz)
920606 (460V, 3Ø, 60 Hz)

Downfl ow Performance Chart

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open

2.0 Turns

Open ‡

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.8

CFM

3198

3056

2914

RPM

1078

1056

1033

kW

1.86

1.70

1.54

0.9

CFM

3259

3013

2877

2741

RPM

1110

1080

1058

1036

kW

1.94

1.77

1.62

1.47

1.0

CFM

3240

3047

2853

2708

2563

RPM

1144

1113

1082

1060

1038

kW

1.92

1.81

1.69

1.51

1.33

1.1

CFM

3431

3244

3056

2862

2667

2491

RPM

1205

1176

1146

1116

1085

1063

kW

2.32

2.07

1.82

1.67

1.51

1.38

1.2

CFM

3294

3096

2898

2677

2456

RPM

1207

1178

1148

1117

1086

kW

2.16

1.98

1.79

1.62

1.45

1.3

CFM

3298

3113

2917

2721

RPM

1239

1210

1181

1151

kW

2.24

2.05

1.89

1.72

1.4

CFM

3348

3147

2946

2742

RPM

1271

1242

1213

1184

kW

2.39

2.14

1.88

1.71

1.5

CFM

3182

2966

2750

RPM

1274

1245

1215

kW

2.32

2.06

1.80

1.6

CFM

3433

3230

3026

2804

RPM

1330

1304

1277

1249

kW

2.57

2.36

2.15

1.96

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger

Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 15. Blower Performance for R6GP-090*-200C Units

(7.5 Ton Downfl ow Models Only)

Advertising