R6GP-072*-100C

MSD kits:
920609 (208-230V, 3Ø, 60 Hz)
920560 (460V, 3Ø, 60 Hz)

Downfl ow Performance Chart

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open ‡

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.8

CFM

RPM

kW

0.9

CFM

2619

2336

2096

RPM

979

951

924

kW

1.14

0.96

0.86

1.0

CFM

2607

2312

2043

RPM

1008

984

956

kW

1.23

1.06

0.88

1.1

CFM

2535

2332

2010

RPM

1035

1012

988

kW

1.23

1.11

0.88

1.2

CFM

2743

2529

2225

2004

RPM

1089

1065

1039

1016

kW

1.48

1.27

1.06

0.97

1.3

CFM

2475

2231

2042

RPM

1094

1069

1043

kW

1.28

1.13

1.01

1.4

CFM

2512

2176

2046

RPM

1125

1099

1074

kW

1.38

1.16

1.08

1.5

CFM

2450

2266

RPM

1154

1129

kW

4.38

1.23

1.6

CFM

2292

RPM

1159

kW

1.34

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 11. Blower Performance for R6GP-072* Units