Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 18

Advertising
background image

18

R6GP-072*-166C

MSD kits:
920613 (208-230V, 3Ø, 60 Hz)
920618 (460V, 3Ø, 60 Hz)

Horizontal Flow Performance Chart*

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open ‡

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.8

CFM

RPM

kW

0.9

CFM

2755

2510

2265

RPM

981

956

930

kW

1.18

1.04

0.90

1.0

CFM

2732

2511

2240

1968

RPM

1013

987

960

933

kW

1.28

1.09

0.95

0.81

1.1

CFM

2714

2470

2225

RPM

1042

1017

991

kW

1.31

1.14

0.98

1.2

CFM

2708

2456

2214

RPM

1073

1047

1021

kW

1.41

1.21

1.02

1.3

CFM

2722

2446

2170

RPM

1103

1077

1051

kW

1.44

1.26

1.08

1.4

CFM

2696

2454

2204

RPM

1131

1105

1082

kW

1.54

1.31

1.11

1.5

CFM

2706

2473

2351

RPM

1159

1137

1107

kW

1.54

1.36

1.23

1.6

CFM

2713

2426

2232

RPM

1187

1166

1143

kW

1.66

1.43

1.27

*

Requires horizontal conversion kit. Please refer to unit TSL for kit number.

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 14. Blower Performance for R6GP-072*-166C Units