Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 20

Advertising
background image

20

R6GP-090*-200C

MSD kits:
920607 (208-230V, 3Ø, 60 Hz)
920606 (460V, 3Ø, 60 Hz)

Horizontal Flow Performance Chart*

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open

2.0 Turns

Open ‡

2.5 Turns

Open

3.0 Turns

Open

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

0.8

CFM

3310

2993

RPM

1019

979

kW

1.75

1.50

0.9

CFM

3492

3185

2878

RPM

1066

1028

990

kW

1.90

1.65

1.40

1.0

CFM

3549

3339

3020

2700

RPM

1102

1074

1039

1004

kW

2.00

1.80

1.55

1.30

1.1

CFM

3347

3107

2808

2508

RPM

1108

1080

1046

1012

kW

1.90

1.70

1.45

1.20

1.2

CFM

3423

3149

2875

2583

RPM

1140

1112

1084

1053

kW

2.00

1.75

1.50

1.30

1.3

CFM

3435

3223

2950

RPM

1172

1144

1118

kW

2.10

1.80

1.60

1.4

CFM

3502

3196

2889

2668

RPM

1207

1179

1150

1126

kW

2.20

1.95

1.70

1.40

1.5

CFM

3520

3281

2969

2657

RPM

1238

1212

1184

1155

kW

2.40

2.10

1.85

1.60

1.6

CFM

3317

3063

2776

RPM

1242

1216

1189

kW

2.25

2.00

1.75

*

Requires horizontal conversion kit. Please refer to unit TSL for kit number.

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 16. Blower Performance for R6GP-090*-200C Units

(7.5 Ton Horizontal Models Only)