PRE-INSTALLATION INFORMATION &

INSTALLATION METHOD

Before You Begin
It is recommended that prior to a kit selection for a retrofi t
installation, the existing duct system be inspected for security
and possible improvements. The removal of fl exible duct
sections or replacement of under sized ducts can signifi cantly
improve a buildings air distribution system for increased unit
effi ciency, correction of room stratifi cation issues for personal
comfort and reduction of equipment noise levels transferred
through the ducts.

Some local codes require testing a buildings duct system for
external air infi ltration and correcting any defi cient structures.
Commercial duct systems should be designed for compliance
with the guidelines given in the ASHRAE Handbooks, ACCA
Manual Q, SMACNA manuals or as specifi ed by any applicable
NFPA and local codes or ordinances that may apply. Improving
an existing duct system could be more cost effective then
increasing the units airfl ow when weighed against the increased
energy cost for the designed life of the equipment.

Always make sure all equipment installation instructions are
on-hand and reviewed prior to the commencement of any work
for the unit and all fi eld installed accessories. This accessory kit
should be installed prior to the installation of any economizers,
air-dampers, or other kits that require the blower operation
for fi nal setup. On roof top installations, these kits could be
partially installed at ground level prior to the fi nal unit placement
in order to reduce the number of crane operations required.

Pre-Installation Checklist
• Verify the HSDK matches the unit application and building

voltage requirements in Table 2 (page 3).

• Inspect the kit and verify the contents to Table 1 (page 1).
• Inspect the duct system for security, air leakage or infi ltration,

and that it is properly constructed for the airfl ow/pressure
requirements of the HSDK.

• Review all equipment and accessory installation instructions

prior to beginning the installation.

• Verify that the unit supply wiring, unit disconnect & over-

current protection is sized properly for the addition of the
HSDK and any other accessory kits that will utilize the same
electrical circuit. See Figure 9 (page 10) for recommended
procedure on how to determine the proper 3 phase wire size.

MOTOR

PART

NUMBER

RATED

HP

POLES

VOLTAGE

HZ

Ø

RATED

RPM

NEMA

NOM.

EFF.

NEMA

FRAME

SIZE

MOTOR AMPERAGE

REQUIRED

EXTERNAL

PROTECTOR

FLA

SF

SFA

621819

3

4

200-230

60

3

1725

81% †

145T

9.10 - 8.90

1.15

10.2 - 9.70

- N/A -

621820

3

4

460

60

3

1725

81% †

145T

4.4

1.15

4.8

- N/A -

622006

5

4

208-230/460

60

3

1760

87.5%

184T

14.0 - 13.4 / 6.7

1.15

15.0 - 15.0 / 7.5

YES

190 / 380

50

3

1445

84%

15.9 / 7.9

1.00

15.9 / 7.9

622026

2

4

208-230/460

60

3

1755

85.5%

145T

5.8 - 5.5 / 2.8

1.15

6.6 - 6.1 / 3.1

YES

622074

3

4

208-230/460

60

3

1765

86.5%

182T

8.8 - 8.6 / 4.4

1.15

10.1 - 9.9 / 5.0

YES

190 / 380

50

3

1455

84%

9.8 / 4.9

1.00

9.8 / 4.9

622254

2

4

208-230/460

60

3

1725

84% †

145T

6.2 - 5.8 / 2.9

1.15

7.0 - 6.6 / 3.3

- N/A -

622305

1.5

4

208-230/460

60

3

1755

86.5%

145T

4.4 - 4.2 / 2.1

1.15

5.0 - 4.6 / 2.3

YES

NOTES:

FLA = Full Load Amps
SF = Service Factor
† Approximate Effi ciency

SFA = Service Factor Amps
Nom. Eff. = Nominal Effi ciency

Table 3. High Static Drive Motor Data

HSDK Installation Method
1. Set the thermostat and unit disconnect(s) to the OFF position.

Verify that the unit has been isolated from all electrical
power sources. For HSDK’s that do not require a motor
replacement, go to step 6.

2. Open/remove the access panels for the units control

panel, blower compartment and fi eld wiring compartments.
NOTE: Never lift or hoist a unit without the access panels
installed or closed and securely attached with all of the
screws supplied from the factory. Refer to the unit installation
instructions for additional details if necessary.

3. Locate the blower motor and trace the motor wires back to

the blower motor contactor or external motor relay. Carefully
cut any zip-ties to free the motor wires from the unit or wiring
harness.

4. Disconnect the motor wires from the overload relay or

contactor T1, T2 & T3 terminals or box lugs.

5. Remove the factory motor & lead assembly from the motor

mounting plate and install the HSDK motor & lead assembly
in the unit. See Figure 1 (page 5) for overload relay mounting
locations.

6. Install the motor overload relay (if required) as described

on page 5. Re-route the blower motor wires to the overload
or blower contactor and secure with the supplied zip-ties.

• Refer to Table 1 to determine the HSDK motor part number

and then Table 3 to determine the service factor amps (SFA)
for the HSDK motor at the correct unit supply voltage. Set
the external overload relay to the motor SFA for that voltage.
NOTE: Replacement overload relay part numbers can be
found using the data in Tables 3 & 4.

7. Verify the proper operation of the motor sheave. Refer to the

blower chart called out for the application in Table 1 and set
the sheave to the proper set-point. Install the HSDK blower
pulley and belt and reference the instructions on pages 6 - 8.
Tighten the belt and secure the assembly.

8. Verify that all electrical connections have been made and

wiring properly secured. Complete the instructions on
verifying the electrical phase balance and blower rotation
direction (pages 8 - 9).

9. After the completion of any other unit or accessory installation

requirements, close or re-install the blower compartment
access panel and restore the electrical power to the unit.
Verify that the unit is delivering the proper airfl ow as described
on pages 8 - 9.

10. Replace all other access panels and refer to the unit

installation instructions to complete the installation and
place the unit into normal service.