Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual

Page 30

Advertising
background image

30

R6GP-090*-200C

HSD kits:
920559 (208-230V, 3Ø, 60 Hz)
920558 (460V, 3Ø, 60 Hz)

Horizontal Flow Performance Chart*

‡ Indicates Factory Sheave Setting for Pre-confi gured Units

External

Unit Static

(in-Wg)

Operating @

230 or 460

Volts

Adjustable Motor Sheave Setting

Fully

Closed

1/2 Turn

Open

1 Turn

Open

1.5 Turns

Open

2.0 Turns

Open

2.5 Turns

Open

3.0 Turns

Open ‡

3.5 Turns

Open

4.0 Turns

Open

4.5 Turns

Open

5.0 Turns

Open

5.5 Turns

Open

6.0 Turns

Open

1.2

CFM

3524

RPM

1160

kW

2.16

1.3

CFM

3495

3344

RPM

1190

1167

kW

2.30

2.08

1.4

CFM

3491

3339

3186

RPM

1220

1196

1171

kW

2.41

2.17

1.93

1.5

CFM

3545

3316

3137

2958

RPM

1247

1226

1202

1178

kW

2.53

2.27

2.07

1.86

1.6

CFM

3391

3145

2941

2736

RPM

1254

1232

1208

1183

kW

2.37

2.14

1.90

1.66

1.7

CFM

3458

3215

2971

2736

RPM

1282

1260

1237

1214

kW

2.54

2.28

2.01

1.74

1.8

CFM

3538

3273

3016

2758

RPM

1313

1289

1265

1241

kW

2.69

2.39

1.92

1.44

1.9

CFM

3383

3123

2840

RPM

1319

1296

1272

kW

2.55

2.24

1.74

2.0

CFM

3543

3447

3181

2915

RPM

1364

1350

1325

1299

kW

2.87

2.65

2.36

2.07

*

Requires horizontal conversion kit. Please refer to unit TSL for kit number.

Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.

3862

Indicates a recommended unit operational point

1159

3.03

3493

Indicates an allowable setting that is not recommended for unit operation

† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.

1017

2.07

Indicates a setting that is not permitted for unit operation

Table 26. Blower Performance for R6GP-090*-200C Units

(7.5 Ton Horizontal Models Only)

Advertising