6�- TECHNICAL FEATURES

AC Power supply

Rated voltage

230 / 120 V ~ Self-powered

Tolerance

80% ... 115 % Un

Frequency (Fn)

50 / 60 Hz

Consumption

< 2 W / 10 VA

Voltage measurement circuit

Rated voltage (Un)

230 V ~

Voltage measurement margin

± 20% Un

Frequency measurement margin

± 2% Fn

Current measurement circuit

Nominal current (In)

10 A Direct

Maximum current

40 A

Start-up current

< 20mA

Self-consumption of the current circuit

< 0.2 VA @ 10A

Measurement accuracy

Active energy measurement

Class 1 (IEC 62053-21)

Reactive energy measurement

Class 2 (IEC 62053-23)

Calculation and Processing

Microprocessor

ARM Cortex M3

Converter

16-bit

Memory

Data

RAM type, stored by Lithium battery

Setup, events, load curve

Non-volatile FLASH memory

Battery

Type

Lithium

Service life

> 15 years @ 35ºC under normal Dispenser operation

Clock

Source

Self-compensated quartz crystal oscillator

Drift

< 0.5 seconds/day at 25ºC

Auxiliary relay

Maximum voltage, open contacts

250V ~

Maximum current

3A ~

Maximum switching power

750 VA

Electrical working life (250 VAC / 5A)

1x10

5

operations

Mechanical working life

2 x10

7

operations

RS-485 Communications

Field bus

RS-485

Communications protocol

Modbus RTU

Baud rate

9600-19200-38400 bauds

Stop bits

1

Parity

none