5�5�2�1�- OPERATION INDICATORS

indiC

L1

L40

Figure 108:Operation Indicators Menu�

This menu displays the information of the operation indicators. It is used for checking all the ba-

sic aspects of the correct operation of the unit during installation or in subsequent on-site tests.

Table 36: Operation indicator menu screens�

Screens

L1

1.13.38

0

Active quadrant, indicates the direction of active or reactive energy or the quadrant.

Range of values: 1, 2, 3, 4.

L1

1

1.12.38

Presence of voltage, indicates the presence of voltage in each phase.

Range of values: 1, Voltage in L1. 2, Voltage in L2

3, Voltage in L3. Blank, no voltage

L1

0

1.11.38

Direction of current, indicates the direction of the current in each phase.

Range of values ( L1, L2, L3): . 1, import 2, export.

0, no current.

L1

L1

1.18.128

1

Active contract tariff, indicates the tariff that is currently active when the contract

is read.

L1

L1

n

0.96.5.0

Alarms, indicates the alarms that have been activated in the unit.

Range of values: C, critical alarm. n, non-critical alarm

b, battery alarm.

L1

00.50

kW

0.135.0

Adjusted power limit

96